Faults and Alarms
List of faults and alarms
3-1728
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
A35224 (N)
TM: Zero mark synchronization interrupted
Drive object:
TM41
Reaction:
NONE
Acknowledge:
NONE
Cause:
The zero mark synchronization with the encoder to be emulated was interrupted.
Alarm value (r2124, interpret decimal):
0: The encoder is not in the ready state (e.g. encoder parked)
1: An absolute encoder was connected.
2: The encoder r0479[0...2] interconnected with CI: p4420 is already communicating with another TM41 (precisely
one TM41 can be interconnected with a specific r0479[0...2]).
3: The BICO interconnection to Terminal Module 41 (TM41) was removed (CI: p4420 = 0 signal).
4: The encoder connected with CI: p4420 has carried out an EDS changeover (this operation is not supported, set
p4420 to 0 and interconnect again).
5: The maximum number of revolutions of the encoder was exceeded.
6: Encoder in an invalid state.
7: Encoder in an invalid state.
8: Encoder in an invalid state (the encoder is not parameterized or the interconnected signal source is not in the cyclic
state).
Remedy:
None necessary.
- if the encoder changes into the ready state, then a synchronization operation that was previously interrupted is car-
ried out again.
- if the synchronization was interrupted due to the maximum permissible synchronization duration, then a new syn-
chronization is not carried out.
- for an absolute encoder, no synchronization is carried out, the zero mark is always output at the zero revolution of
the TM41.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
A35225
TM: Zero mark synchronization held - encoder not in the ready state
Drive object:
TM41
Reaction:
NONE
Acknowledge:
NONE
Cause:
The zero mark synchronization with the encoder to be emulated was held.
The encoder is not in the "ready" state.
Remedy:
Bring the encoder into the "ready" state.
A35226
TM: Tracks A/B are de-activated
Drive object:
TM41
Reaction:
NONE
Acknowledge:
NONE
Cause:
The output of tracks A/B of the Terminal Module 41 (TM41) has been held (frozen). This means:
The encoder emulation of the TM41 hardware is enabled (this is necessary so that no TRI state of the AB tracks
occurs). The hardware receives a setpoint of zero so that no motion occurs at the TM41 AB tracks.
Reasons for Alarm 35226:
- CI: p4420 was not interconnected (in this case, the encoder emulation of the hardware is de-activated)
- the encoder is not in the "ready" state (parking encoder or non-parameterized encoder data set).
- for TM41 there is an additional fault.
Remedy:
- establish an interconnection from CI: p4420.
- bring the encoder into the "ready" state.
- remove any TM41 faults.
A35227
TM: Zero mark synchronization interrupted - EDS changeover not supported
Drive object:
TM41
Reaction:
NONE
Acknowledge:
NONE
Cause:
The interconnected encoder has carried out an EDS changeover.
Terminal Module 41 (TM41) does not support this particular application case.
Remedy:
Bring the encoder into the ready state, carry out RAM to ROM and then Power On.
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...