List of parameters
Parameters
1-305
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Sets the ramp-down time for the internal ramp-function generator for the motorized potentiometer.
The setpoint is changed from the speed/velocity limit (p1082) to zero within this time (if no initial rounding-off has
been activated).
Dependency:
Refer to: p1030, p1047, p1082
Note:
The deceleration time is extended corresponding to the activated initial rounding-off (p1030.2).
Description:
Sets the effective setpoint after the internal motorized potentiometer ramp-function generator.
This setpoint is the output value of the motorized potentiometer and must be appropriately interconnected onwards
(e.g. with the main setpoint).
Recommend.:
Interconnect the signal with main setpoint (p1070).
Dependency:
Refer to: p1070
Note:
For "With ramp-function generator", after an OFF1, OFF2, OFF3 or for a 0 signal via BI: p0852 (inhibit operation,
cancel pulses) the ramp-function generator output (r1050) is set to the starting value (configuration via p1030.0).
Description:
Sets the effective setpoint after the internal motorized potentiometer ramp-function generator.
This setpoint is the output value of the motorized potentiometer and must be appropriately interconnected onwards
(e.g. with the main setpoint).
Recommend.:
Interconnect the signal with main setpoint (p1070).
Dependency:
Refer to: p1070
Note:
For "With ramp-function generator", after an OFF1, OFF2, OFF3 or for a 0 signal via BI: p0852 (inhibit operation,
cancel pulses) the ramp-function generator output (r1050) is set to the starting value (configuration via p1030.0).
p1048[0...n]
Motorized potentiometer ramp-down time / Mop ramp-down time
SERVO (Extended
setp), VECTOR
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
3020
P-Group:
Setpoints
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.000 [s]
1000.000 [s]
10.000 [s]
r1050
CO: Motor. potentiometer setpoint after the ramp-function generator /
Mop setp after RFG
SERVO (Extended
setp), VECTOR
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
1550, 3020
P-Group:
Setpoints
Units group:
3_1
Unit selection:
p0505
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- [RPM]
- [RPM]
- [RPM]
r1050
CO: Motor. potentiometer setpoint after the ramp-function generator /
Mop setp after RFG
SERVO (Extended
setp, Lin)
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
1550, 3020
P-Group:
Setpoints
Units group:
4_1
Unit selection:
p0505
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- [m/min]
- [m/min]
- [m/min]
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...