Description:
The programmable characteristic for the V/f control is defined using 4 points and 0 Hz/p1310.
This parameter specifies the voltage of the third point along the characteristic.
Dependency:
The following applies to the frequency values: p1320 <= p1322 <= p1324 <= p1326. Otherwise, a standard charac-
teristic is used that contains the rated motor operating point.
Refer to: p1310, p1311, p1320, p1321, p1322, p1323, p1325, p1326, p1327
Description:
The programmable characteristic for the V/f control is defined using 4 points and 0 Hz/p1310.
This parameter specifies the voltage of the third point along the characteristic.
Dependency:
Refer to: p1310, p1311, p1320, p1321, p1322, p1323, p1324, p1326, p1327
Description:
In the servo control mode the following applies:
The linear characteristic for the V/f control is defined by 0 Hz / p1319 and p1326 / p1327.
For vector control, the following applies:
The programmable characteristic for the V/f control is defined using 4 points and 0 Hz/p1310.
This parameter specifies the voltage of the fourth point along the characteristic.
Dependency:
In the servo control mode the following applies:
Activates the V/f control using p1317.
For vector control, the following applies:
Selects the freely programmable characteristic using p1300 = 3.
The following applies to the frequency values: p1320 <= p1322 <= p1324 <= p1326. Otherwise, a standard charac-
teristic is used that contains the rated motor operating point.
Refer to: p1310, p1311, p1317, p1319, p1320, p1321, p1322, p1323, p1324, p1325, p1327
Note:
In the servo control mode the following applies:
Linear interpolation is carried out between the points 0 Hz / p1319 and p1326 / p1327.
For vector control, the following applies:
Linear interpolation is carried out between the points 0 Hz / p1310, p1320 / p1321 ... p1326 / p1327. For output fre-
quencies above p1326, the characteristic is extrapolated with the gradient between the characteristic points
p1324/p1325 and p1326/p1327.
The voltage boost when accelerating (p1311) is also applied to the freely programmable V/Hz characteristic.
p1324[0...n]
V/f control programmable characteristic frequency 3 / Uf char f3
VECTOR
Can be changed:
U, T
Calculated:
CALC_MOD_ALL
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
6300
P-Group:
V/f open-loop control
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.00 [Hz]
3000.00 [Hz]
0.00 [Hz]
p1325[0...n]
V/f control programmable characteristic voltage 3 / Uf char U3
VECTOR
Can be changed:
U, T
Calculated:
CALC_MOD_ALL
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
6300
P-Group:
V/f open-loop control
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.0 [Vrms]
10000.0 [Vrms]
0.0 [Vrms]
p1326[0...n]
V/f control programmable characteristic frequency 4 / Uf char f4
SERVO, VECTOR
Can be changed:
U, T
Calculated:
CALC_MOD_REG
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
5300, 6300
P-Group:
V/f open-loop control
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.00 [Hz]
10000.00 [Hz]
0.00 [Hz]
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...