![Siemens SINAMICS S Series Скачать руководство пользователя страница 1010](http://html.mh-extra.com/html/siemens/sinamics-s-series/sinamics-s-series_list-manual_12654271010.webp)
Parameters
List of parameters
1-1010
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Sets the velocity tolerance for the "Safe Acceleration Monitor".
Dependency:
Refer to: C01706
Note:
A change only becomes effective after a POWER ON.
SBR: Safe Acceleration Monitor
Description:
Sets the velocity tolerance that is used for a 2-encoder system in crosswise comparison between the two monitor-
ing channels.
Dependency:
Refer to: p9501, p9542
Note:
If the "actual value synchronization" is not enabled (p9501.3 = 0), then the value parameterized in p9542 is used as
tolerance in the data cross-check.
A change only becomes effective after a POWER ON.
Description:
Sets the velocity tolerance that is used for a 2-encoder system in crosswise comparison between the two monitor-
ing channels.
Dependency:
Refer to: p9501, p9542
Note:
If the "actual value synchronization" is not enabled (p9501.3 = 0), then the value parameterized in p9542 is used as
tolerance in the data cross-check.
A change only becomes effective after a POWER ON.
Description:
Sets the tolerance time for the changeover of the safety-related inputs (SGE).
Note:
A change only becomes effective after a POWER ON.
p9548
SI motion SBR actual velocity tolerance (Control Unit) / SI Mtn SBR tol
SERVO (Safety rot),
VECTOR (Safety rot)
Can be changed:
C2
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.00 [RPM]
120000.00 [RPM]
300.00 [RPM]
p9549
SI motion slip velocity tolerance (Control Unit) / SI Mtn slip tol
SERVO, VECTOR
Can be changed:
C2
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.00 [mm/min]
6000.00 [mm/min]
6.00 [mm/min]
p9549
SI motion slip velocity tolerance (Control Unit) / SI Mtn slip tol
SERVO (Safety rot),
VECTOR (Safety rot)
Can be changed:
C2
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.00 [RPM]
6000.00 [RPM]
6.00 [RPM]
p9550
SI motion SGE changeover tolerance time (Control Unit) / SI Mtn SGE_chg tol
SERVO, VECTOR
Can be changed:
U, T
Calculated:
-
Access level:
4
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.00 [ms]
10000.00 [ms]
500.00 [ms]
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...