Parameters
List of parameters
1-510
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Dependency:
Refer to: p1958, p1960
Notice:
The step p1959.8 (identify q inductance on the test stand) may only be selected if the drive can be kept at zero
speed or at a fixed velocity either using a test stand or other mechanical measures.
During steps p1959.2 (identifying the moment of inertia) and p1959.6 (identifying the force constant) the Vdc_min
controller is disabled (p1240).
During step p1959.7 (identifying the reluctance force constant) the Vdc_min controller and Vdc_max controller are
disabled (p1240).
Note:
For an induction motor (ASM), the following bits are effective: 1, 2, 5, 8, 9, 10, 14, 15
For a synchronous motor (SRM), the following bits are effective: 2, 5, 6, 7, 8, 10, 14, 15
Re bit 05:
For "motor holding brake the same as sequence control" (p1215 = 1 or 3), the Lq characteristic is only measured up
to approximately the rated motor current (p0305) instead of up to the current limit (p0640). Before carrying out the
rotation measurement for motors with brake, the brake should be opened (p1215 = 2) - as long as this can be done
without incurring any danger.
Re bit 10:
If the motor holding brake is set just the same as the sequence control (p1215 = 1 or 3), the commutation angle and
the direction of rotation are not measured. Before carrying out the rotation measurement for motors with brake, the
brake should be opened (p1215 = 2) - as long as this can be done without incurring any danger.
Re bit 14 and 15:
The following applies for bit 14 and 15 = 0:
When the function module "extended setpoint channel" is activated (r0108.8 = 1), the direction inhibit of the setpoint
channel becomes effective. No direction of inhibit is effective if the function module is inactive.
The following applies for minimum bit 14 = 1 or bit 15 = 1:
The direction inhibit set in p1959 becomes effective.
Description:
Sets the configuration of the rotating measurement.
Dependency:
Refer to: F07988
Note:
The encoder is only tested if the rotating measurement with encoder is selected (p1960 = 2).
The following parameters are influenced for the individual optimization steps:
Bit 00: None
07
Identifying the reluctance force constant
Yes
No
-
08
Identifying the q inductance at the test stand Yes
No
-
09
Identifying the magnetizing current / magne-
tizing inductance
Yes
No
-
10
Identifying the commutation angle and
direction of rotation
Yes
No
-
14
Clockwise direction of rotation permitted
Yes
No
-
15
Counter-clockwise direction of rotation per-
mitted
Yes
No
-
p1959[0...n]
Rotating measurement configuration / Rot meas config
VECTOR (n/M)
Can be changed:
T
Calculated:
CALC_MOD_ALL
Access level:
2
Data type:
Unsigned16
Dynamic index:
DDS, p0180
Func. diagram:
-
P-Group:
Motor identification
Units group:
-
Unit selection:
-
Not for motor type:
REL
Expert list:
1
Min Max
Factory
setting
-
-
0001 1111 bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Enc test active
Yes
No
-
01
Saturation characteristic identification
Yes
No
-
02
Moment of inertia identification
Yes
No
-
03
Recalculates the speed controller parame-
ters
Yes
No
-
04
Speed controller optimization, (vibration
test)
Yes
No
-
05
q leakage inductance ident. (for current con-
troller adaptation)
Yes
No
-
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...