Faults and Alarms
List of faults and alarms
3-1736
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
A35905 (F, N)
TM: Parameter access
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The Control Unit attempted to write an illegal parameter value into the Terminal Module.
Remedy:
- check whether the firmware version of the Terminal Module (r0158) matches the firmware version of Control Unit
(r0018).
- if required, replace the Terminal Module.
Note:
The firmware versions that match each other are in the readme.txt file on the CompactFlash card.
Reaction upon F:
NONE
Acknowl. upon F:
IMMEDIATELY (POWER ON)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
A35906 (F, N)
TM: 24 V power supply missing
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The 24 V power supply for the digital outputs is missing.
Alarm value (r2124, interpret hexadecimal):
01: TM17 24 V power supply for DI/DO 0 ... 7 missing.
02: TM17 24 V power supply for DI/DO 8 ... 15 missing.
04: TM15 24 V power supply for DI/DO 0 ... 7 (X520) missing.
08: TM15 24 V power supply for DI/DO 8 ... 15 (X521) missing.
10: TM15 24 V power supply for DI/DO 16 ... 23 (X522) missing.
20: TM41 24 V power supply for DI/DO 0 ... 3 missing.
Remedy:
Check the terminals for the power supply voltage (L1+, L2+, L3+, M).
Reaction upon F:
NONE
Acknowl. upon F:
IMMEDIATELY (POWER ON)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
A35907 (F, N)
TM: Hardware initialization error
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The Terminal Module was not successfully initialized.
Alarm value (r2124, interpret hexadecimal):
01: TM17 or TM41 - incorrect configuration request.
02: TM17 or TM41 - programming not successful.
04: TM17 or TM41 - invalid time stamp
Remedy:
Carry out a POWER ON.
Reaction upon F:
NONE
Acknowl. upon F:
IMMEDIATELY (POWER ON)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
A35910 (F, N)
TM: Module overtemperature
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The temperature in the module has exceeded the highest permissible limit.
Remedy:
- reduce the ambient temperature.
- replace the Terminal Module.
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...