![Siemens SINAMICS S Series Скачать руководство пользователя страница 274](http://html.mh-extra.com/html/siemens/sinamics-s-series/sinamics-s-series_list-manual_1265427274.webp)
Parameters
List of parameters
1-274
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Sets the send and receive telegram.
Values:
3:
Standard telegram 3, PZD-5/9
999:
Free telegram configuration with BICO
Dependency:
Refer to: F01505, F01506
Note:
If a value is not equal to 999, a telegram is set and the automatically set interconnections in the telegram are inhib-
ited.
The inhibited interconnections can only be changed again after setting value 999.
Description:
Sets the send and receive telegram.
Values:
0:
Free telegram configuring with p0915/p0916
Description:
Sets the number of tolerated consecutive sign-of-life errors of the clock-cycle synchronous master.
The sign-of-life signal is normally received in PZD4 (control word 2) from the master.
Dependency:
Refer to: p2045, r2065
Refer to: F01912
Note:
The sign-of-life monitoring is disabled for p0925 = 65535.
Description:
Displays the operating mode.
1: Closed-loop speed controlled operation with ramp-function generator
2: Closed-loop position controlled operation
3: Closed-loop speed controlled operation without ramp-function generator
p0922
PROFIdrive telegram selection / PD Telegr_sel
TM41
Can be changed:
C2(1), T
Calculated:
-
Access level:
1
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
1520, 2420,
2422, 2423, 2460, 2470
P-Group:
Communications
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
3 999
999
p0922
PROFIdrive telegram selection / PD Telegr_sel
TM15, TM17
Can be changed:
C2(1), T
Calculated:
-
Access level:
1
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
2481, 2483
P-Group:
Communications
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 0
0
p0925
PROFIdrive clock synchronous sign-of-life tolerance / PD SoL_tol
CU_CX32, CU_S,
SERVO, TM41, VEC-
TOR (n/M)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
2410
P-Group:
Communications
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 65535
1
r0930
PROFIdrive operating mode / PD operating mode
SERVO, VECTOR
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
-
P-Group:
Setpoints
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...