List of parameters
Parameters
1-205
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
If a parameter change is rejected, it should be checked as to whether the input terminal is already being used in
p0488, p0489, p0495, p0680, p2517 or p2518.
Description:
Sets the edge to evaluate the measuring probe signal for speed actual value measurement.
0: 0/1 edge
1: 1/0 edge
Dependency:
Refer to: p0580
Description:
Sets the number of pulses per revolution (e.g. for disks with holes).
Description:
Sets the maximum measuring time for the measuring probe.
If a new pulse is not received before the maximum measuring time has expired, then the speed actual value in
r0586 is set to zero. This timer stage is re-started with the next pulse.
Dependency:
Refer to: r0586
Description:
Displays the speed actual value measured using the BERO.
Dependency:
Refer to: p0580, p0583
Note:
For p0580 = 0 (no measuring probe), a value of zero is displayed here.
p0581
Meas probe, edge / MT edge
SERVO
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Integer16
Dynamic index:
-
Func. diagram:
-
P-Group:
Encoder
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 1
0
p0582
Measuring probe, pulses per revolution / MT pulses per rev
SERVO
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
-
P-Group:
Encoder
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
1 12
1
p0583
Measuring probe, maximum measuring time / MT t_meas max
SERVO
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Encoder
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.040 [s]
10.000 [s]
10.000 [s]
r0586
CO: Measuring probe, speed actual value / MT n_act
SERVO
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Displays, signals
Units group:
3_1
Unit selection:
p0505
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- [RPM]
- [RPM]
- [RPM]
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...