Parameters
List of parameters
1-112
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
6:
MICROMASTER 440 PX
7:
MICROMASTER 430
100:
SINAMICS S
101:
SINAMICS S
120:
PM340 (SINAMICS S120)
150:
SINAMICS G
200:
SINAMICS GM
250:
SINAMICS SM
300:
SINAMICS GL
Note:
For parallel circuit configurations, the parameter index is assigned to a power unit.
Description:
Displays the properties supported by the power unit hardware.
Note:
For parallel circuit configurations, the parameter index is assigned to a power unit.
Description:
Overloading the load duty cycles applies under the prerequisite that before and after the overload, the drive con-
verter is operated with its base load current - in this case, a load duty cycle of 300 s is used as basis.
For booksize drive units, the following applies:
Only the setting p0205 = 0 can be selected. In this particular case, the base load current has a load duty cycle of
150 % for 60 s and 176 % for 30 s.
For chassis drive units, the following applies:
The base load current for a slight overload condition is based on a load duty cycle 110 % for 60 s and 150 % for 10
s.
The base load current for a high overload condition is based on a load duty cycle 150 % for 60 s and 160 % for 10 s.
Values:
0:
Load duty cycle with high overload for vector drives
1:
Load duty cycle with low overload for vector drives
6:
S1 duty cycle for servo drives (feed drive)
7:
S6 duty cycle for servo drives (spindle drive)
r0204[0...n]
Power unit hardware properties / PU HW property
A_INF, B_INF,
SERVO, S_INF,
VECTOR
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dynamic index:
PDS, p0120
Func. diagram:
-
P-Group:
Converter
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Device type
DC/AC device
AC/AC device
-
01
RFI filter available
Yes
No
-
02
Active Line Module available
Yes
No
-
03
Smart Line Module available
Yes
No
-
04
Basic Line Module available with thyristor
bridge
Yes
No
-
05
Basic Line Module available with diode
bridge
Yes
No
-
06
Liquid cooling
Yes
No
-
08
Internal Braking Module
Yes
No
-
09
Different cooling type supported
Yes
No
-
12
Safe Brake Control (SBC) supported
No
Yes
-
p0205
Power unit application / PU application
VECTOR
Can be changed:
C2(1)
Calculated:
-
Access level:
2
Data type:
Integer16
Dynamic index:
-
Func. diagram:
-
P-Group:
Converter
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 7
6
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...