List of parameters
Parameters
1-761
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Dependency:
Refer to: p3863
Refer to: F30027
Warning:
It must be carefully ensured that the binector outputs BO: p3864.n are correctly interconnected and also that the
appropriate digital outputs are correctly connected-up.
If the interconnection/connection is incorrect, in the case of an active DC link fast discharge, the software could exe-
cute another function (incorrect function) via binector outputs BO: p3864.n or could also permanently control the DC
link fast discharge even if the line contactor is closed.
Note:
The DC link fast discharge is only possible for "booksize" formats. This function is not supported for "chassis" for-
mats.
Description:
Sets the signal source for the signal "pre-alarm I*t shutdown (X21.3) of the Braking Module.
BI: p3865[0...7] = 0 signal --> no pre-alarm, I*t shutdown
BI: p3865[0...7] = 1 signal --> pre-alarm I*t shutdown (A06901)
Dependency:
Refer to: A06901
Note:
The pre-alarm I*t shutdown is only possible for "booksize" formats. This function is not supported for "chassis" for-
mats.
Description:
Sets the signal source for the "fault" signal of the Braking Module (X21.4 for "booksize" formats and X21.3 for
"chassis" formats).
BI: p3866[0...7] = 0 signal --> fault (A06900)
BI: p3866[0...7] = 1 signal --> No fault
For a 1 signal, an acknowledgement via BO: r3861 is automatically carried out at certain time intervals.
Dependency:
Refer to: A06900
Description:
Sets the configuration when operating a long stator motor.
Dependency:
Refer to: p3871, p3872, p3873, p3874, r3875, p3876, p3878, p3879
05
Fast discharge Braking Module 6
High
Low
-
06
Fast discharge Braking Module 7
High
Low
-
07
Fast discharge Braking Module 8
High
Low
-
p3865[0...7]
BI: Braking Module pre-warning I*t shutdown / BM I*t shutdown
A_INF (Brk Mod ext),
B_INF (Brk Mod ext),
S_INF (Brk Mod ext)
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dynamic index:
-
Func. diagram:
9951
P-Group:
-
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
0
p3866[0...7]
BI: Braking Module fault / BM fault
A_INF (Brk Mod ext),
B_INF (Brk Mod ext),
S_INF (Brk Mod ext)
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dynamic index:
-
Func. diagram:
9951
P-Group:
-
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
0
p3870
Long stator configuration / Long stator config
SERVO
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
-
P-Group:
-
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
0000
bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Activate long stator help functions
Active
Inactive
-
01
Suppress Gx_ZSW.14
Active
Inactive
-
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...