Parameters
List of parameters
1-282
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Values:
0:
Inactive
1:
Hardware-Reset immediate
2:
Hardware reset preparation
3:
Hardware reset after cyclic communication has failed
Danger:
It must be absolutely ensured that the system is in a safe condition.
It is not permissible that the CompactFlash card of the Control Unit is accessed.
Notice:
For SIMOTION or SINUMERIK with integrated SINAMICS, the hardware reset acts on the complete system and
depends on the state of the control.
Note:
Re value = 1:
Reset is immediately executed and communications interrupted.
After communications have been established, check the reset operation (refer below).
Re value = 2:
Help to check the reset operation.
Firstly, set p0972 = 2 and then read back. Secondly, set p0972 = 1 (it is possible that this request is possibly no
longer acknowledged). The communication is then interrupted.
After communications have been established, check the reset operation (refer below).
Re value = 3:
The reset is executed after interrupting cyclic communication. This setting is used to implement a synchronized
reset by a control for several drive units.
If the cyclic communication is active for both PROFIdrive interfaces, then the reset is executed after completing
both cycle communications.
After communications have been established, check the reset operation (refer below).
To check the reset operation:
After the drive unit has been restarted and communications have been established, read p0972 and check the fol-
lowing:
p0972 = 0? --> The reset was successfully executed.
p0972 > 0? --> The reset was not executed.
Description:
Displays the identification of the drive object.
Index:
[0] = Company (Siemens = 42)
[1] = Drive object type
[2] = Firmware version
[3] = Firmware date (year)
[4] = Firmware date (day/month)
[5] = PROFIdrive drive object, type class
[6] = PROFIdrive drive object, sub-type Class 1
[7] = Drive object number
[8] = Reserved
[9] = Reserved
[10] = Firmware patch/hot fix
Note:
Example:
r0975[0] = 42 --> SIEMENS
r0975[1] = 11 --> SERVO drive object type
r0975[2] = 102 --> first part, firmware version V01.02 (second part, refer to index 10)
r0975[3] = 2003 --> year 2003
r0975[4] = 1401 --> 14th of January
r0975[5] = 1 --> PROFIdrive drive object, type class
r0975[0...10]
Drive object identification / DO identification
All objects
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
-
P-Group:
Communications
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...