Description:
Sets the sampling time for the inputs and outputs of the Terminal Board 30 (TB30).
Index:
[0] = Digital inputs/outputs (DI/DO)
[1] = Analog inputs (AI)
[2] = Analog outputs (AO)
Dependency:
The parameter can only be modified for p0009 = 3, 29.
The sampling times can only be set as an integer multiple of the basic sampling time (r0110, r0111).
Refer to: p0009, r0110, r0111
Note:
The modified sampling time is not effective until the drive unit is powered-up again.
For clock cycle synchronous PROFIBUS operation, the TB30 hardware (e.g. A/D converter ) is operated with the
PROFIBUS clock cycle (r2064[1]). This clock cycle is also kept after the PROFIBUS connection has been exited up
to the next time that the Control Unit is powered-down. In this case, a faster sampling time than the PROFIBUS
clock cycle is not practical in p4099[0...2].
Description:
Sets the sampling time for the inputs and outputs of terminal module 31 (TM31).
Index:
[0] = Digital inputs/outputs (DI/DO)
[1] = Analog inputs (AI)
[2] = Analog outputs (AO)
Dependency:
The parameter can only be modified for p0009 = 3, 29.
The sampling times can only be set as an integer multiple of the basic sampling time (r0110, r0111).
Refer to: p0009, r0110, r0111
Notice:
The sampling times entered in index 0 (digital inputs/outputs) and index 2 (analog outputs) must always be greater
than or equal to the sampling time in index 1 (analog inputs).
Note:
- the modified sampling time is not effective until the drive unit is powered-up again.
- P4099(0) must never equal zero.
p4099[0...2]
TB30 inputs/outputs, sampling time / TB30 I/O t_sample
TB30
Can be changed:
C1(3)
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
9100, 9102,
9104, 9106
P-Group:
Commands
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.00 [µs]
5000.00 [µs]
[0] 4000.00 [µs]
[1] 4000.00 [µs]
[2] 4000.00 [µs]
p4099[0...2]
TM31 inputs/outputs, sampling time / TM31 I/O t_sample
TM31
Can be changed:
C1(3)
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
9550
P-Group:
Commands
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.00 [µs]
5000.00 [µs]
4000.00 [µs]
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...