List of faults and alarms
Faults and Alarms
3-1597
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Re fault 125:
Reduce cable resistance (p0352).
Re fault 126:
Reduce series inductance (p0353).
Re fault 127, 128, 129:
It is possible that current controller is oscillating. Reduce p1715 before next measurement.
Re fault 130:
Do not initiate a drive data set changeover during motor ident. routine.
Re fault value 140:
Before the measurement, enable at least one direction of rotation (value of p1110 = 0 or value of p1111 = 0 or
p1959.14 = 1 or p1959.15 = 1).
Re fault value = 160:
- extend accelerating time when determining kT, moment of inertia and reluctance torque, e.g. by increasing max.
speed (p1082), increasing moment of inertia or reducing max. current (p0640).
- in sensorless operation with load moment of inertia, parameterize the load moment of inertia (p1498).
- reduce the ramp-up time (p1958).
- increase speed controller P-gain (p1460).
- suppress meas. (p1959).
Re fault value 173:
-
Re fault value 180:
Increase max. speed (p1082).
Reduce p1755.
Suppress meas. (p1909, p1959).
Re fault value 190:
Set speed setpoint to zero.
Re fault value 191:
Do not start motor data ident. routine while motor is still rotating.
Re fault value = 192:
Check closed-loop speed control (motor rotor may be locked or closed-loop speed control is not functioning).
For p1215 = 1, 3 (brake the same as the sequence control) check the control sense (p0410.0).
Ensure that enable signals are present during measurement.
Remove any pulling loads from motor.
Increase max. current (p0640).
Reduce max. speed (p1082).
Suppress meas. (p1959).
Re fault value 193:
The motor has moved through more than 5° electrical (r0093). Lock motor rotor at one of these pole position angles
(r0093): 90°, 210° or 330° (+- 5°) and then start identification.
Re fault value 194:
Switch-out all supplementary torques (e.g. CI:p1511).
For hanging/suspended axes: Lock motor rotor at one of these pole position angles (r0093): 90°, 210° or 330° (+-
1°) and then start identification.
Re fault value 195:
De-select closed-loop torque control (p1300 = 21 or 20, or set the signal source in p1501 to a 0 signal).
Re fault value = 200, 201:
- set pulse frequency to 0.5 * current controller frequency (e.g. 4 kHz for a current controller clock cycle of 125 us).
- reduce cable length between Motor Module and motor.
- read-out measured values (r1950, r1951) and therefore determine suitable values for p1952, p1953 according to
your own estimation.
A07991 (N)
Drive: Motor data identification activated
Drive object:
SERVO
Reaction:
NONE
Acknowledge:
NONE
Cause:
The motor data ident. routine is activated.
The motor data identification routine is carried out at the next power-on command.
See also: p1910 (Motor data identification routine, stationary (standstill)), p1960 (Rotating measurement selection)
Remedy:
None necessary.
The alarm automatically disappears after the motor data identification routine has been successfully completed or
for the setting p1910 = 0 or p1960 = 0.
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...