List of parameters
Parameters
1-743
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Displays the velocities in filter branch 1.
Index:
[0] = Filter 1.1 input value
[1] = Filter 1.1 output value
Description:
Sets the signal source to increase the voltage for external line-drive synchronization.
BI: p3784 = 1 signal:
The voltage is increased.
Note:
Only SINAMICS GM150.
Description:
Sets the signal source to decrease the voltage for external line-drive synchronization.
BI: p3785 = 1 signal:
The voltage is lowered.
Note:
Only SINAMICS GM150.
Description:
Sets the activation for the line-drive synchronization.
Values:
0:
Sync-line-drive de-activated
1:
Sync-line-drive activated VSM-INT
Dependency:
Refer to: p3801, p3802
Note:
When the ground fault monitoring initiates a fault for overlapping synchronizing the threshold value p0287[1] for the
Motor Module and the associated infeed must be appropriately increased (e.g. p0287[1] = 100 %).
For p3800 = 1, the following applies:
r3777[0...1]
CO: APC filter branch 1 display values / APC branch 1 val
SERVO (APC, Lin)
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
7012
P-Group:
Setpoints
Units group:
4_1
Unit selection:
p0505
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- [m/min]
- [m/min]
- [m/min]
p3784[0...n]
BI: Sync-line-drive external increase voltage / Sync ext V incr
VECTOR
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Unsigned32 / Binary
Dynamic index:
CDS, p0170
Func. diagram:
-
P-Group:
Functions
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
0
Min Max
Factory
setting
- -
0
p3785[0...n]
BI: Sync-line-drive external decrease voltage / Sync ext V decr
VECTOR
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Unsigned32 / Binary
Dynamic index:
CDS, p0170
Func. diagram:
-
P-Group:
Functions
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
0
Min Max
Factory
setting
- -
0
p3800[0...n]
Sync-line-drive activation / Sync act
VECTOR
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Integer16
Dynamic index:
DDS, p0180
Func. diagram:
7020
P-Group:
Functions
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 1
0
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...