Parameters
List of parameters
1-136
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Sets the rated motor power factor (cos phi, rating plate).
For a parameter value of 0.000, the power factor is internally calculated and displayed in r0332.
Dependency:
This parameter is only available for IEC motors (p0100 = 0).
Refer to: p0100, p0309, r0332
Caution:
This parameter is automatically preset for motors from the motor list (p0301). When selecting a catalog motor, this
parameter cannot be changed (write protection). Information in p0300 should be carefully observed when removing
write protection.
Note:
The parameter is not used for synchronous motors (p0300 = 2xx).
The parameter is automatically preset for motors from the motor list (p0301).
Description:
Sets the rated motor efficiency (rating plate).
For a parameter value of 0.0, the power factor is internally calculated and displayed in r0332.
Dependency:
This parameter is only available for NEMA motors (p0100 = 1).
Refer to: p0100, p0308, r0332
Caution:
This parameter is automatically preset for motors from the motor list (p0301). When selecting a catalog motor, this
parameter cannot be changed (write protection). Information in p0300 should be carefully observed when removing
write protection.
Note:
The parameter is not used for synchronous motors (p0300 = 2xx).
The parameter is automatically preset for motors from the motor list (p0301).
Description:
Sets the rated motor frequency (rating plate).
Dependency:
The number of pole pairs (r0313) is automatically re-calculated when the parameter is changed (together with
p0311), if p0314 = 0.
Refer to: p0311, r0313, p0314
Caution:
This parameter is automatically preset for motors from the motor list (p0301). When selecting a catalog motor, this
parameter cannot be changed (write protection). Information in p0300 should be carefully observed when removing
write protection.
Note:
The parameter is automatically pre-assigned for induction motors from the motor list (p0301).
For synchronous motors, the parameter is not required and must therefore be pre-assigned zero. For p0310 = 0, it
is not possible to calculate the pole pair; instead, it must be entered in p0314.
p0308[0...n]
Rated motor power factor / Mot cos_phi_rated
SERVO, VECTOR
Can be changed:
C2(1, 3)
Calculated:
-
Access level:
1
Data type:
Floating Point
Dynamic index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor
Units group:
-
Unit selection:
-
Not for motor type:
PEM, REL
Expert list:
1
Min Max
Factory
setting
0.000 1.000
0.000
p0309[0...n]
Rated motor efficiency / Mot eta_rated
VECTOR
Can be changed:
C2(1, 3)
Calculated:
-
Access level:
1
Data type:
Floating Point
Dynamic index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor
Units group:
-
Unit selection:
-
Not for motor type:
PEM, REL
Expert list:
1
Min Max
Factory
setting
0.0 [%]
99.9 [%]
0.0 [%]
p0310[0...n]
Rated motor frequency / Mot f_rated
SERVO
Can be changed:
C2(1, 3)
Calculated:
-
Access level:
1
Data type:
Floating Point
Dynamic index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.00 [Hz]
3000.00 [Hz]
0.00 [Hz]
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...