List of parameters
Parameters
1-811
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Sets the normalization characteristic for the analog outputs of terminal module 31 (TM31).
The normalization characteristic for the analog outputs is defined using 2 points.
This parameter specifies the y coordinate (output voltage in V or output current in mA) of the 2nd value pair of the
characteristic.
Index:
[0] = AO 0 (X522.1, X522.2, X522.3)
[1] = AO 1 (X522.4, X522.5, X522.6)
Dependency:
The units of this parameter (V or mA) depend on the analog input type.
Refer to: r4076, p4076
Notice:
This parameter is automatically overwritten when the analog output type is changed (p4076).
Note:
This parameter is overwritten if p4076 (type of analog output) is changed.
The parameters for the characteristic do not limit.
Description:
Sets the signal source for inverting the analog output signals of the Terminal Board 30 (TB30).
Index:
[0] = AO 0 (X482.5/X482.6)
[1] = AO 1 (X482.7/X482.8)
Description:
Sets the signal source to invert the analog output signals of terminal module 31 (TM31).
Index:
[0] = AO 0 (X522.1, X522.2, X522.3)
[1] = AO 1 (X522.4, X522.5, X522.6)
Description:
Sets the offset for the analog outputs of Terminal Board 30 (TB30).
The offset is added to the output signal after the normalization characteristic.
p4080[0...1]
TM31 analog outputs, characteristic value y2 / TM31 AO char y2
TM31
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
9572
P-Group:
Terminals
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
-20.000 [V]
20.000 [V]
10.000 [V]
p4082[0...1]
BI: TB30 analog outputs, signal source for inversion / TB30 AO invert
TB30
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dynamic index:
-
Func. diagram:
9106
P-Group:
Terminals
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
0
p4082[0...1]
BI: TM31 analog outputs, signal source for inversion / TM31 AO invert
TM31
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dynamic index:
-
Func. diagram:
9572
P-Group:
Terminals
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
0
p4083[0...1]
TB30 analog outputs, offset / TB30 AO offset
TB30
Can be changed:
U, T
Calculated:
-
Access level:
1
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
9106
P-Group:
Terminals
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
-10.000 10.000
0.000
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...