List of parameters
Parameters
1-37
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Sets the mode of the operating display for the Basic Operator Panel (BOP) in the operating states "ready" and
"operation".
Values:
0:
Operation --> r0021, otherwise r0020 <--> r0021
1:
Operation --> r0021, otherwise r0020
2:
Operation --> p0005, otherwise p0005 <--> r0020
3:
Operation --> r0002, otherwise r0002 <--> r0020
4:
p0005
Dependency:
Refer to: p0005
Note:
Mode 0 ... 3 can only be selected if also r0020, r0021 are available on the drive object.
Mode 4 is available for all drive objects.
Description:
Sets the delay time until the background lighting of the Basic Operator Panel (BOP) is switched-off.
If no keys are actuated, then the background lighting automatically switches itself off after this time has expired.
Note:
p0007 = 0: Background lighting is always switched on (factory setting).
Description:
Sets the required drive object that is active at the Basic Operator Panel (BOP) after booting.
Note:
The value from p0008 initializes the display on the Basic Operator Panel (BOP) at the top left after booting.
The drive object Control Unit is selected using the value 1.
Description:
Sets the device and basic drive commissioning.
By appropriately setting this parameter, those parameters are filtered that can be written into in the various commis-
sioning steps.
p0006
BOP operating display mode / BOP op_ disp mode
A_INF, B_INF,
SERVO, S_INF,
VECTOR
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Integer16
Dynamic index:
-
Func. diagram:
-
P-Group:
-
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 4
4
p0007
BOP background lighting / BOP lighting
CU_S
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dynamic index:
-
Func. diagram:
-
P-Group:
-
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 [s]
2000 [s]
0 [s]
p0008
BOP drive object after booting / BOP DO select
CU_S
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
-
P-Group:
-
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
1 65535
1
p0009
Device commissioning parameter filter / Dev comm par_filt
CU_CX32, CU_S
Can be changed:
C1, T
Calculated:
-
Access level:
1
Data type:
Integer16
Dynamic index:
-
Func. diagram:
-
P-Group:
-
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 50
1
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...