Parameters
List of parameters
1-440
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Sets the signal source for the scaling of the lower torque limiting to limit the speed controller output.
Description:
Sets the signal source for the torque/force reduction when traversing to a fixed stop. This value is converted into a
factor and is interconnected to the scaling of the torque/force limits.
Dependency:
Refer to: p1528, p1529, r1543, p1544, p1545
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description:
Sets the signal source for the torque/force reduction when traversing to a fixed stop. This value is converted into a
factor and is interconnected to the scaling of the torque/force limits.
Dependency:
Refer to: p1528, p1529, r1543, p1544, p1545
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description:
Displays the internally converted factor to interconnect to the scaling of the torque/force limits.
Dependency:
Refer to: p1528, p1529, p1542, p1544, p1545
p1541[0...n]
CI: Torque limit. speed controller lower scaling / M_max nctr lowScal
VECTOR (n/M)
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / FloatingPoint32
Dynamic index:
CDS, p0170
Func. diagram:
6060
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
REL
Expert list:
1
Min Max
Factory
setting
- -
1
p1542[0...n]
CI: Travel to fixed stop torque reduction / TfS M_red
SERVO
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / FloatingPoint32
Dynamic index:
CDS, p0170
Func. diagram:
5610
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
0
p1542[0...n]
CI: Travel to fixed stop force reduction / TfS F_red
SERVO (Lin)
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / FloatingPoint32
Dynamic index:
CDS, p0170
Func. diagram:
5610
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
0
r1543
CO: Travel to fixed stop torque scaling / TfS M scal
SERVO
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
5610
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- [%]
- [%]
- [%]
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...