Faults and Alarms
List of faults and alarms
3-1468
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
A01482
Topology: Comparison Sensor Module missing in the actual topology
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected a Sensor Module in the target topology that is not available in the actual topol-
ogy.
Alarm value (r2124, interpret decimal):
Component number of the additional target components.
Note:
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Remedy:
- re-configure the drive belonging to the Sensor Module in the commissioning software project (encoder configura-
tion) and download the new configuration into the drive unit.
- delete the drive belonging to the Sensor Module in the commissioning software project and download the new con-
figuration into the drive unit.
- check that the actual topology matches the target topology and if required, change over.
- check DRIVE-CLiQ cables for interruption and contact problems.
Note:
Under "Topology --> Topology view" the commissioning software offers improved diagnostics capability (e.g. set-
point/actual value comparison).
A01483
Topology: Comparison Terminal Module missing in the actual topology
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected a Terminal Module in the target topology that is not available in the actual
topology.
Alarm value (r2124, interpret decimal):
Component number of the additional target components.
Note:
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Remedy:
- delete the Terminal Module in the commissioning software project and download the new configuration into the
drive unit.
- check that the actual topology matches the target topology and if required, change over.
- check DRIVE-CLiQ cables for interruption and contact problems.
Note:
Under "Topology --> Topology view" the commissioning software offers improved diagnostics capability (e.g. set-
point/actual value comparison).
A01484
Topology: Comparison DMC missing in the actual topology
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected a DRIVE-CLiQ Hub Module Cabinet (DMC) in the target topology that is not
available in the actual topology.
Alarm value (r2124, interpret decimal):
Component number of the additional target components.
Note:
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Remedy:
- delete the DRIVE-CLiQ Hub Module Cabinet (DMC) in the commissioning software project and download the new
configuration into the drive unit.
- check that the actual topology matches the target topology and if required, change over.
- check DRIVE-CLiQ cables for interruption and contact problems.
Note:
Under "Topology --> Topology view" the commissioning software offers improved diagnostics capability (e.g. set-
point/actual value comparison).
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...