List of parameters
Parameters
1-123
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Sets the run-up time of the cooling system after a power-off command.
Description:
Displays the control word for the cooling system.
Description:
Sets the signal sources for the feedback signals from the cooling system.
Index:
[0] = Cooling system powered-up
[1] = Cooling system ready to be powered-up
[2] = Cooling system, no alarm present
[3] = Cooling system, no fault present
[4] = Cooling system, no leaked liquid
[5] = Cooling system liquid flow OK
[6] = Cooling system, conductivity < fault threshold
[7] = Cooling system, conductivity < alarm threshold
p0264
Cooling system, run-on time / RKA run-on time
A_INF (Cooling sys-
tem), B_INF (Cool-
ing system), SERVO
(Cooling system),
S_INF (Cooling sys-
tem), VECTOR
(Cooling system)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
9795
P-Group:
Converter
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.0 [s]
180.0 [s]
30.0 [s]
r0265.0...3
BO: Cooling system, control word / RKA ctrl word
A_INF (Cooling sys-
tem), B_INF (Cool-
ing system), SERVO
(Cooling system),
S_INF (Cooling sys-
tem), VECTOR
(Cooling system)
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned8
Dynamic index:
-
Func. diagram:
-
P-Group:
Commands
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Power-up cooling system
Power-up
Deactivating
-
01
Message, converter off
Off
On
-
02
Acknowledge faults
Acknowledgement
No acknowledgement
-
03
Leakage sensing OK
No leaked liquid
Leaked liquid
-
p0266[0...7]
BI: Cooling system, feedback signals, signal source / RKA fdbk S_src
A_INF (Cooling sys-
tem), B_INF (Cool-
ing system), SERVO
(Cooling system),
S_INF (Cooling sys-
tem), VECTOR
(Cooling system)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dynamic index:
-
Func. diagram:
-
P-Group:
Communications
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
1
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...