Parameters
List of parameters
1-452
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
If the difference again lies within the bandwidth, the I component of the excitation current flux controller is re-acti-
vated and the I component of the flux controller of the field-generating current is reduced as an exponential function
with respect to time. The reduction of the I component over time depends on the rotor time constant (r0384).
Description:
Sets the proportional gain of the P flux controller for separately-excited synchronous motors.
Note:
The value is automatically pre-assigned dependent on the motor when the drive system is first commissioned.
When calculating controller parameter (p0340 = 4), this value is re-calculated.
Description:
Displays the output of the P flux controller for separately-excited synchronous motors (FEM).
Description:
Sets the stator current setpoint for operation of separately-excited synchronous motors (FEM) in the operating
mode I/f (p1300 = 18).
Description:
Sets the static torque setpoint for sensorless vector control (SLVC). This parameter is entered as a percentage
referred to the rated motor torque (r0333).
For sensorless vector control, when the motor model is shut down, an absolute current is impressed. p1610 repre-
sents the maximum load that occurs at a constant setpoint speed.
Notice:
p1610 should always be set to at least 10 % higher than the maximum steady-state load that can occur.
Note:
For p1610 = 0%, a current setpoint is calculated that corresponds to the no-load case (rated magnetizing current).
For p1610 = 100 %, a current setpoint is calculated that corresponds to the rated motor torque.
p1600[0...n]
P flux controller, P gain / P flux ctrl Kp
VECTOR (n/M)
Can be changed:
U, T
Calculated:
CALC_MOD_CON
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
-
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
ASM, PEM, REL
Expert list:
1
Min Max
Factory
setting
0.0 999999.0
10.0
r1602
CO: Flux controller P output / Flux ctrl P outp
VECTOR (n/M)
Can be changed:
-
Calculated:
-
Access level:
4
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Closed-loop control
Units group:
6_2
Unit selection:
p0505
Not for motor type:
ASM, PEM, REL
Expert list:
1
Min Max
Factory
setting
- [Arms]
- [Arms]
- [Arms]
p1609[0...n]
Current setpoint for I/f operation / I_set I/f oper
VECTOR (n/M)
Can be changed:
U, T
Calculated:
CALC_MOD_ALL
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
6727
P-Group:
Closed-loop control
Units group:
6_2
Unit selection:
p0505
Not for motor type:
ASM, PEM, REL
Expert list:
1
Min Max
Factory
setting
0.00 [Arms]
10000.00 [Arms]
0.00 [Arms]
p1610[0...n]
Torque setpoint static (SLVC) / M_set static
VECTOR (n/M)
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
-
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
REL, FEM
Expert list:
1
Min Max
Factory
setting
0.0 [%]
200.0 [%]
50.0 [%]
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...