List of parameters
Parameters
1-939
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Sets and displays the CANopen NMT state.
Values:
0:
Initializing
4:
Stopped
5:
Operational
127:
Pre-operational
128:
Reset node
129:
Reset Communication
Note:
The value 0 (initialization) is only displayed and cannot be set.
Description:
Sets the communication parameters for CANopen Receive Process Data Object 1 (RPDO 1).
Index:
[0] = PDO COB-ID
[1] = PDO transmission type
Dependency:
A valid COB-ID can only be set for the available (existing) channel.
Refer to: p8740, p8741
Note:
Corresponds to the CANopen object 1400 hex + 40 hex * x (x: Drive number 0 ... 7).
Transmission types 0, 1, FE and FF can be set.
PDO: Process Data Object
Description:
Sets the communication parameters for CANopen Receive Process Data Object 2 (RPDO 2).
Index:
[0] = PDO COB-ID
[1] = PDO transmission type
Dependency:
A valid COB-ID can only be set for the available (existing) channel.
Refer to: p8740, p8741
Note:
Corresponds to the CANopen object 1401 hex + 40 hex * x (x: Drive number 0 ... 7).
Transmission types 0, 1, FE and FF can be set.
PDO: Process Data Object
p8685
CBC NMT states / NMT states
CU_S (CAN)
Can be changed:
C1(1), U, T
Calculated:
-
Access level:
3
Data type:
Integer16
Dynamic index:
-
Func. diagram:
-
P-Group:
Communications
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 129
127
p8700[0...1]
CBC receive PDO 1 / Receive PDO 1
SERVO (CAN), VEC-
TOR (CAN)
Can be changed:
C1(3), T
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dynamic index:
-
Func. diagram:
9204, 9206
P-Group:
Communications
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0000 hex
8000 06DF hex
[0] 8000 06DF hex
[1] 00FE hex
p8701[0...1]
CBC receive PDO 2 / Receive PDO 2
SERVO (CAN), VEC-
TOR (CAN)
Can be changed:
C1(3), T
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dynamic index:
-
Func. diagram:
9204, 9206
P-Group:
Communications
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0000 hex
8000 06DF hex
[0] 8000 06DF hex
[1] 00FE hex
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...