List of parameters
Parameters
1-273
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Values:
1:
Standard telegram 1, PZD-2/2
2:
Standard telegram 2, PZD-4/4
3:
Standard telegram 3, PZD-5/9
4:
Standard telegram 4, PZD-6/14
20:
Standard telegram 20, PZD-2/6
352:
SIEMENS telegram 352, PZD-6/6
999:
Free telegram configuration with BICO
Dependency:
Refer to: F01505, F01506
Caution:
Telegrams 2, 3 and 4 are not suitable for sensorless vector control (p1300 = 20). For sensorless vector control, it is
necessary that the setpoint speed is entered at the ramp-function generator input (e.g. p1070) and not after the
ramp-function generator (p1155).
Note:
If a value is not equal to 999, a telegram is set and the automatically set interconnections in the telegram are inhib-
ited.
The inhibited interconnections can only be changed again after setting value 999.
Description:
Sets the send and receive telegram.
Values:
999:
Free telegram configuration with BICO
Dependency:
Refer to: F01505, F01506
Caution:
Telegrams 2, 3 and 4 are not suitable for sensorless vector control (p1300 = 20). For sensorless vector control, it is
necessary that the setpoint speed is entered at the ramp-function generator input (e.g. p1070) and not after the
ramp-function generator (p1155).
Note:
If a value is not equal to 999, a telegram is set and the automatically set interconnections in the telegram are inhib-
ited.
The inhibited interconnections can only be changed again after setting value 999.
Description:
Sets the send and receive telegram.
Values:
7:
Standard telegram 7, PZD-2/2
9:
Standard telegram 9, PZD-6/5
110:
SIEMENS telegram 110, PZD-12/7
999:
Free telegram configuration with BICO
Dependency:
Refer to: F01505, F01506
Caution:
Telegrams 2, 3 and 4 are not suitable for sensorless vector control (p1300 = 20). For sensorless vector control, it is
necessary that the setpoint speed is entered at the ramp-function generator input (e.g. p1070) and not after the
ramp-function generator (p1155).
Note:
If a value is not equal to 999, a telegram is set and the automatically set interconnections in the telegram are inhib-
ited.
The inhibited interconnections can only be changed again after setting value 999.
p0922
PROFIdrive telegram selection / PD Telegr_sel
VECTOR (Pos ctrl)
Can be changed:
C2(1), T
Calculated:
-
Access level:
1
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
1520, 2420,
2422, 2423, 2460, 2470
P-Group:
Communications
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
999 999
999
p0922
PROFIdrive telegram selection / PD Telegr_sel
VECTOR (EPOS)
Can be changed:
C2(1), T
Calculated:
-
Access level:
1
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
1520, 2420,
2422, 2423, 2460, 2470
P-Group:
Communications
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
7 999
999
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...