List of parameters
Parameters
1-459
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Displays the output of the excitation current monitoring for separately excited synchronous motors.
Description:
Sets the signal source for the individual feedback signals from the excitation.
Index:
[0] = Excitation ready to be powered-up
[1] = Excitation ready
[2] = Excitation operational
[3] = Excitation group signal fault
[4] = Excitation, group signal alarm
[5] = Not used
[6] = Not used
Dependency:
Refer to: r1649
Description:
Sets the monitoring time of the excitation.
After an ON command, the feedback signal must be received within this monitoring time.
Note:
After the on command for the excitation (r1648.0 = 1), its feedback signal must be available at r1649.1 within this
monitoring time (BI: p1645[1]).
The same monitoring time is effective after the excitation is enabled for operation (r1648.3 = 1) up to the feedback
signal "excitation in operation" (r1649.2 = 1, BI: p1645[2]).
Description:
Sets the switch-off delay time to shut-down the excitation equipment.
Note:
The delay time starts if, when powering-down, r0863.0 = 0.
r1648.0 and r1648.3 are reset at the end of the delay time.
r1644
Excitation current monitoring output / I_exc_monit outp
VECTOR (n/M)
Can be changed:
-
Calculated:
-
Access level:
4
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
6727
P-Group:
Closed-loop control
Units group:
6_2
Unit selection:
p0505
Not for motor type:
ASM, PEM, REL
Expert list:
1
Min Max
Factory
setting
- [Arms]
- [Arms]
- [Arms]
p1645[0...6]
BI: Excitation feedback signals signal source / Exc FS S_src
VECTOR (n/M)
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dynamic index:
-
Func. diagram:
6495
P-Group:
Commands
Units group:
-
Unit selection:
-
Not for motor type:
ASM, PEM, REL
Expert list:
1
Min Max
Factory
setting
- -
1
p1646
Excitation monitoring time / Excit t_monit
VECTOR (n/M)
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
6495
P-Group:
Commands
Units group:
-
Unit selection:
-
Not for motor type:
ASM, PEM, REL
Expert list:
1
Min Max
Factory
setting
2.0 [s]
1300.0 [s]
20.0 [s]
p1647
Excitation switch-out delay time / Exc t_off
VECTOR (n/M)
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
6495
P-Group:
Commands
Units group:
-
Unit selection:
-
Not for motor type:
ASM, PEM, REL
Expert list:
1
Min Max
Factory
setting
0.5 [s]
5.0 [s]
0.8 [s]
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...