List of parameters
Parameters
1-385
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
- it is not permissible that OFF1, OFF3 or STOP2 are active.
- it is not permissible that the motor data identification is active.
- it is not permissible that the master control is active.
The following conditions can mean that the DSC function is not active in spite of the fact that the bit is set:
- clock-cycle synchronous operation is not selected (r2054 not equal to 4).
- the PROFIBUS is not clock-cycle synchronous (r2064[0] not equal to 1).
- DSC is not switched-in on the control side; this means that KPC = 0 is transferred as value at CI: p1191.
Description:
Displays the status word of the speed controller.
Description:
Displays the status word of the closed-loop current control.
Note:
The selected current limit is taken into account by the upstream torque limiting; this is the reason that bits 6, 7 and
8 are only set for overshoots due to the current setpoint filter.
r1407.0...14
CO/BO: Status word speed controller / ZSW n_ctrl
VECTOR (n/M)
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
1530, 2522
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
REL
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
V/f control active
Yes
No
-
01
Sensorless operation active
Yes
No
-
02
Torque control active
Yes
No
6030
03
Speed control active
Yes
No
6040
05
Speed controller I component frozen
Yes
No
6040
06
Speed controller I component set
Yes
No
6040
07
Torque limit reached
Yes
No
6060
08
Upper torque limit active
Yes
No
-
09
Lower torque limit active
Yes
No
-
10
Droop enabled
Yes
No
6030
11
Speed setpoint limited
Yes
No
6030
12
Ramp-function generator set
Yes
No
-
13
Sensorless operation due to a fault
Yes
No
-
14
I/f control active
Yes
No
-
r1408.0...9
CO/BO: Status word closed-loop current control / ZSW curr ctrl
SERVO
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
2530, 5040
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
REL
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Cl-loop curr ctrl
Active
Not active
-
04
Limit Vd
Active
Not active
-
05
Limit Vq
Active
Not active
-
06
Positive limiting Iq
Active
Not active
-
07
Negative limiting Iq
Active
Not active
-
08
Limit iq_set
Active
Not active
-
09
Limit id_set
Active
Not active
-
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...