Parameters
List of parameters
1-1038
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Sets the delay time of the pulse cancelation for the function "Safe Stop 1" (SS1) on the Motor Module to brake
along the OFF3 down ramp (p1135).
Dependency:
Refer to: p1135, p9652
Note:
For a data cross-check between p9652 and p9852, a difference of one Safety monitoring clock cycle is tolerated.
The parameterized time is internally rounded-off to an integer multiple of the monitoring clock cycle.
SS1: Safe Stop 1 (corresponds to Stop Category 1 acc. to EN60204)
Description:
Sets the transition period from STOP F to STOP A on the Motor Module.
Dependency:
Refer to: p9658, r9895
Refer to: F30611
Note:
For a data cross-check between p9658 and p9858, a difference of one Safety monitoring clock cycle is tolerated.
The parameterized time is internally rounded-off to an integer multiple of the monitoring clock cycle.
STOP F: Defect in a monitoring channel (error in the data cross-check)
STOP A: Pulse cancelation via the safety shutdown path
Description:
Displays the Safety Integrated version for the safety functions integrated in the drive on the Motor Module.
Index:
[0] = Safety Version (major release)
[1] = Safety Version (minor release)
[2] = Safety Version (baselevel or patch)
Dependency:
Refer to: r9770, r9890
Note:
Example:
r9870[0] = 2, r9870[1] = 3, r9870[2] = 1 --> Safety-Version V02.03.01
p9852
SI Safe Stop 1 delay time (Motor Module) / SI Stop 1 t_del MM
SERVO, VECTOR
Can be changed:
C2
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.00 [ms]
300000.00 [ms]
0.00 [ms]
p9858
SI transition time STOP F to STOP A (Control Unit) / SI STOP F->A MM
SERVO, VECTOR
Can be changed:
C2
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
2802
P-Group:
Safety Integrated
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.00 [µs]
30000000.00 [µs]
0.00 [µs]
r9870[0...2]
SI version safety functions integrated in drive (Motor Module) / SI version MM
SERVO, VECTOR
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
2802
P-Group:
Safety Integrated
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...