List of parameters
Parameters
1-481
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
- the voltage emulation errors should be identified with the Motor Module in the warm state.
- the motor temperature (r0035) should not change significantly (i.e. it should not be identified immediately after a
load duty cycle).
Re kT(iq) characteristic (p1780.9 = 1):
- for the kT(iq) characteristic kT(iq) = kT + kT3 * iq^2 + kT5 * iq^4 + kT7 * iq^6 the parameters must first be identified
(p1959.6 = 1) (kT: p0316, kT3: p0646, kT5: p0647, kT7: p0647).
Description:
Sets the configuration for the adaptation circuit of the motor model.
Induction motor (ASM): Rs, Rr (only for operation with encoder), Lh and offset compensation.
Permanent magnet synchronous motor (PEM): kT
Note:
ASM: Induction motor
PEM: Permanent magnet synchronous motor
The following applies for the VECTOR closed-loop control type:
When selecting the compensation of the valve interlocking via Rs (bit 7), the compensation in the gating unit is de-
activated and is instead taken into account in the motor model.
Description:
Sets the integral time for the Rs adaptation of the motor model for an induction motor (ASM).
Description:
Displays the corrective value for the Rs adaptation of the motor model for an induction motor (ASM).
p1780[0...n]
Motor model adaptation configuration / MotMod adapt conf
VECTOR
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dynamic index:
DDS, p0180
Func. diagram:
-
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
REL
Expert list:
1
Min Max
Factory
setting
-
-
0111 1100 bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
01
Select motor model ASM Rs adaptation
Yes
No
-
02
Select motor model ASM Lh adaptation
Yes
No
-
03
Select motor model PEM kT adaptation
Yes
No
-
04
Select motor model, offset adaptation
Yes
No
-
05
Select ASM Rr adaptation (only with
encoder)
Yes
No
-
06
Select pole wheel identification PEM sen-
sorless
Yes
No
-
07
Select T(valve) with Rs adaptation
Yes
No
-
p1781[0...n]
Motor model Rs adaptation integral time / MotMod Rs Tn
VECTOR (n/M)
Can be changed:
U, T
Calculated:
CALC_MOD_CON
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
-
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
PEM, REL, FEM
Expert list:
1
Min Max
Factory
setting
10 [ms]
10000 [ms]
100 [ms]
r1782[0...n]
Motor model Rs adaptation corrective value / MotMod Rs corr
VECTOR (n/M)
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
-
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
PEM, REL, FEM
Expert list:
1
Min Max
Factory
setting
- [Ohm]
- [Ohm]
- [Ohm]
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...