List of parameters
Parameters
1-587
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Dependency:
Refer to: r2197
Refer to: A07903
Note:
Re bit 00:
Alarm A07903 is output when the bit is set with p2197.7 = 0 (n_set <> n_act).
Re bit 01:
When the bit is set, the load monitoring is only carried out in the 1st quadrant as a result of the positive characteris-
tic parameters (p2182 ... p2190).
Re bit 15:
The bit indicates as to whether the automatic parameterization (p0340 = 1, p3900 > 0) for the parameters of the
extended monitoring functions was carried out. If the bit is not set, e.g. when activating the configuration (refer to
p0108.15), the parameterization is automatically carried out when booting even if r3925.0 is already 1.
Description:
Configuration word for signals and monitoring functions.
Dependency:
Refer to: r2197
Refer to: A07903
Note:
Re bit 00:
Alarm A07903 is output when the bit is set with p2197.7 = 0 (n_set <> n_act).
Re bit 01:
When the bit is set, the load monitoring is only carried out in the 1st quadrant as a result of the positive characteris-
tic parameters (p2182 ... p2190).
Re bit 15:
The bit indicates as to whether the automatic parameterization (p0340 = 1, p3900 > 0) for the parameters of the
extended monitoring functions was carried out. If the bit is not set, e.g. when activating the configuration (refer to
p0108.15), the parameterization is automatically carried out when booting even if r3925.0 is already 1.
Description:
Sets the hysteresis speed (bandwidth) for the following signals:
"|n_act| < speed threshold value 3" (BO: r2199.0)
"n_set >= 0" (BO: r2198.5)
"n_act >= 0" (BO: r2197.3)
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Enable alarm A07903
Yes
No
8010
01
Load monitoring only in the 1st quadrants
Yes
No
8010
15
Automatic parameterization carried out
(p0340 = 1, p3900 > 0)
Yes
No
-
p2149[0...n]
Monitoring configuration / Monit config
VECTOR
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dynamic index:
DDS, p0180
Func. diagram:
8010
P-Group:
Messages
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
0001
bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Enable alarm A07903
Yes
No
8010
01
Load monitoring only in the 1st quadrants
Yes
No
8010
15
Automatic parameterization carried out
(p0340 = 1, p3900 > 0)
Yes
No
-
p2150[0...n]
Hysteresis speed 3 / n_hysteresis 3
SERVO, VECTOR
Can be changed:
U, T
Calculated:
CALC_MOD_LIM_REF
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
8010
P-Group:
Messages
Units group:
3_1
Unit selection:
p0505
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.00 [RPM]
300.00 [RPM]
2.00 [RPM]
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...