Faults and Alarms
List of faults and alarms
3-1726
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Remedy:
Power-down the unit and power-up again.
If the fault is still present, replace the module/board.
Reaction upon F:
NONE
Acknowl. upon F:
IMMEDIATELY (POWER ON)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
F35207 (N, A)
TM: Temperature fault threshold exceeded
Drive object:
All objects
Reaction:
A_INFEED: OFF2 (NONE, OFF1)
SERVO: OFF2 (NONE, OFF1, OFF3)
VECTOR: OFF2 (NONE, OFF1, OFF3)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The temperature measured using the temperature sensing of the Terminal Module (TM) (r4105) has exceeded the
threshold value to initiate this fault (p4102[1]).
Please note that this fault can only be initiated if the temperature evaluation was activated (p4100 = 2 for KTY sensor
or p4100 = 1 for PTC sensor).
Fault value (r0949, interpret decimal):
The hundred thousands and ten thousands location specifies the component number of the TMxx where the fault
occurred.
Alarm:
Please note that Fault F35207 only causes the drive to be shut down if there is at least one BICO interconnection
between the drive and TM31.
Remedy:
- allow the temperature sensor to cool down.
- if required, set the fault response to NONE (p2100, p2101).
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
A35211 (F, N)
TM: Temperature alarm threshold exceeded
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The temperature measured using the temperature sensing of the Terminal Module (TM) (r4105) has exceeded the
threshold value to initiate this alarm (p4102[0]).
Alarm value (r2124, interpret decimal):
The hundred thousands and ten thousands location specifies the component number of the TMxx where the fault
occurred.
Remedy:
Allow the temperature sensor to cool down.
Reaction upon F:
NONE
Acknowl. upon F:
IMMEDIATELY (POWER ON)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
F35220 (N, A)
TM: Frequency limit reached for signal output
Drive object:
All objects
Reaction:
A_INFEED: OFF1 (NONE, OFF2)
SERVO: OFF1 (NONE, OFF2, OFF3)
VECTOR: OFF1 (NONE, OFF2, OFF3)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The signals output from the Terminal Module 41 (TM41) for tracks A/B have reached the limit frequency. The output
signals are no longer in synchronism with the specified setpoint.
Remedy:
- enter a lower speed setpoint (p1155).
- reduce the encoder pulse number (p0408).
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...