List of faults and alarms
Faults and Alarms
3-1447
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
F01105 (A)
CU: Insufficient memory
Drive object:
All objects
Reaction:
OFF1
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
Too many functions have been configured on this Control Unit e.g. too many drives, function modules, data sets, OA
applications, blocks, etc).
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- change the configuration on this Control Unit (e.g. fewer drive, function modules, data sets, OA applications, blocks,
etc).
- use an additional Control Unit.
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F01107
CU: Save to CompactFlash card unsuccessful
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
A data save on the CompactFlash card was not able to be successfully carried out.
- CompactFlash card is defective.
- CompactFlash card does not have sufficient memory space.
Fault value (r0949, interpret decimal):
-1: The file on the RAM was not able to be opened.
-2: The file on the RAM was not able to be read.
-3: A new directory was not able to be set-up on the CompactFlash card.
-4: A new file was not able to be set-up on the CompactFlash card.
-5: A new file was not able to be written onto the CompactFlash card.
Remedy:
- try to save again.
- use another CompactFlash card.
F01110
CU: More than one SINAMICS G on one Control Unit
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
More than one SINAMICS G power unit type is being operated from the Control Unit.
Fault value (r0949, interpret decimal):
Number of the second drive with a SINAMICS G power unit type.
Remedy:
Only one SINAMICS G drive type is permitted.
F01111
CU: SINAMICS S and G together on one Control Unit
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
SINAMICS S and G drive units are being operated together on one Control Unit.
Fault value (r0949, interpret decimal):
Number of the first drive object with a different power unit type.
Remedy:
Only power units of one particular drive type may be operated with one Control Unit.
F01112
CU: Power unit not permissible
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The connected power unit cannot be used together with this Control Unit.
Fault value (r0949, interpret decimal):
1: Power unit is not supported (e.g. PM240).
2: DC/AC power unit connected to CU310 not permissible.
Remedy:
Replace the power unit that is not permissible by a component that is permissible.
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...