List of parameters
Parameters
1-339
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Note:
A starting attempt starts immediately when a fault occurs. The start attempt is considered to been completed if the
motor was magnetized (r0056.4 = 1) and an additional delay time of 1 s has expired.
As long as a fault is present, an acknowledge command is generated in the time intervals of p1212 / 2. When suc-
cessfully acknowledged, the start counter is decremented. If, after this, a fault re-occurs before a restart has been
completed, then acknowledgement starts again from the beginning.
Fault F07320 is output if, after several faults occur, the number of parameterized start attempts has been reached.
After a successful start attempt, i.e. a fault/error has no longer occurred up to the end of the magnetizing phase, the
start counter is again reset to the parameter value after 1 s. If a fault re-occurs - the parameterized number of start
attempts is again available.
At least one start attempt is always carried out.
After a line supply failure, acknowledgement is immediate and when the line supply returns, the system is powered-
up. If, between successfully acknowledging the line fault and the line supply returning, another fault occurs, then its
acknowledgement also causes the start counter to be decremented.
Description:
Sets the delay time up to restart.
Dependency:
This parameter setting is active for p1210 = 4, 6.
For p1210 = 1, the following applies: Faults are only acknowledged, no restart.
Refer to: p1210, r1214
Caution:
A change is only accepted and made if the state "initialization" (r1214.0) and "wait for alarm" (r1214.1).
Note:
The faults are automatically acknowledged and the system is powered-up again after half of the waiting time has
expired and after the full waiting time has expired.
Description:
Sets the delay time up to restart.
Dependency:
This parameter setting is active for p1210 = 4, 6.
For p1210 = 1, the following applies: Faults are only automatically acknowledged in half of the waiting time, no
restart.
Refer to: p1210, r1214
Caution:
A change is only accepted and made if the state "initialization" (r1214.0) and "wait for alarm" (r1214.1).
Note:
The faults are automatically acknowledged after half of the waiting time has expired and the full waiting time.
If the cause of a fault is not removed in the first half of the delay time, then it is no longer possible to acknowledge in
the waiting time.
p1212
Automatic restart, delay time start attempts / AR t_wait start
A_INF, B_INF,
S_INF
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Functions
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.1 [s]
600.0 [s]
1.0 [s]
p1212
Automatic restart, delay time start attempts / AR t_wait start
SERVO, VECTOR
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Functions
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.1 [s]
600.0 [s]
1.0 [s]
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...