List of faults and alarms
Faults and Alarms
3-1505
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Remedy:
Set the relevant drives to zero speed before starting the function generator.
Note:
The alarm is reset as follows:
- remove the cause of this alarm.
- restart the function generator.
A02015
Function generator: Drive enable signals missing
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The master control and/or enable signals are missing to connect to the specified drive.
Alarm value (r2124, interpret decimal):
Number of the drive object involved.
See also: p4815 (Function generator drive number)
Remedy:
Fetch the master control to the specified drive object and set all enable signals.
Note:
The alarm is reset as follows:
- remove the cause of this alarm.
- restart the function generator.
A02020
Function generator: Parameter cannot be changed
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
This parameter setting cannot be changed when the function generator is active (p4800 = 1).
See also: p4810 (Function generator mode), p4812 (Function generator physical address), p4813 (Function gener-
ator physical address reference value), p4815 (Function generator drive number), p4820 (Function generator signal
shape), p4821 (Function generator period), p4822 (Function generator pulse width), p4823 (Function generator
bandwidth), p4824 (Function generator amplitude), p4825 (Function generator 2nd amplitude), p4826 (Function gen-
erator offset), p4827 (Function generator ramp-up time to offset), p4828 (Function generator lower limit), p4829
(Function generator upper limit)
Remedy:
- stop before parameterizing the function generator (p4800 = 0).
- if required, start the function generator (p4800 = 1).
Note:
The alarm is reset as follows:
- remove the cause of this alarm.
- restart the function generator.
See also: p4800 (Function generator control)
A02025
Function generator: Period too short
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The value for the period is too short.
See also: p4821 (Function generator period)
Remedy:
Check and adapt the value for the period.
Note:
The alarm is reset as follows:
- remove the cause of this alarm.
- restart the function generator.
See also: p4821 (Function generator period)
A02026
Function generator: Pulse width too wide
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The selected pulse width is too high.
The pulse width must be less than the period duration.
See also: p4822 (Function generator pulse width)
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...