Faults and Alarms
List of faults and alarms
3-1516
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
F05058
Parallel circuit: VSM EEPROM versions differ
Drive object:
A_INF, B_INF, SERVO, S_INF, VECTOR
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The EEPROM versions of the Voltage Sensing Modules (VSM) do not match.
Fault value (r0949, interpret decimal):
Parameter in which the first different version number was detected.
Remedy:
For parallel circuit configurations, only Voltage Sensing Modules (VSM) with identical EEPROM versions may be
used.
F05059
Parallel circuit: VSM firmware versions differ
Drive object:
A_INF, B_INF, SERVO, S_INF, VECTOR
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The firmware versions of the Voltage Sensing Module (VSM) do not match.
Fault value (r0949, interpret decimal):
Parameter in which the first different version number was detected.
Remedy:
For parallel circuit configurations, only Voltage Sensing Modules (VSM) with identical firmware versions may be
used.
F05060
Parallel circuit: Power unit firmware version does not match
Drive object:
A_INF, B_INF, SERVO, S_INF, VECTOR
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
Firmware from version V02.30.01.00 is required when connecting the power units in parallel.
Remedy:
Update the firmware of the power units (at least V02.30.01.00).
F05061
Infeed, number of VSM
Drive object:
A_INF, B_INF, SERVO, S_INF, VECTOR
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The number of active Voltage Sensing Modules (VSM) for the drive object infeed with chassis power units is not cor-
rect.
For A_Infeed, each active power unit must be assigned an active VSM also for a parallel circuit configuration.
For S_Infeed, the active drive object, must be assigned at least one active VSM.
Fault value (r0949, interpret decimal):
Number of VSMs that are currently assigned to the drive object.
Remedy:
Adapts the number of active Voltage Sensing Modules (VSM).
F06000
Infeed: Precharging monitoring time expired
Drive object:
A_INF, B_INF, S_INF
Reaction:
OFF2 (OFF1)
Acknowledge:
IMMEDIATELY
Cause:
After the line contactor closes the power unit does not signal the READY state within the monitoring time (p0857).
The end of the DC link pre-charging was not detected due to one of the following reasons:
- there is not line supply voltage.
- the line contactor is not closed.
- the line supply voltage is too low.
- the power unit has detected an internal fault.
- there is a DC link short-circuit.
- the DC link has a ground fault.
- the pre-charging resistors are overheated as there were too many pre-charging operations per time unit.
- the pre-charging resistors are overheated as the DC link capacitance is too high (maximum 20 mF).
- line supply voltage incorrectly set.
See also: p0857 (Power unit monitoring time)
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...