List of parameters
Parameters
1-765
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
p3900 = 2 includes the restoration of the interconnections of PROFIBUS PZD telegram selection (p0922) and the
interconnections via p0700 and the calculations corresponding to p0340 = 1.
p3900 = 3 only includes the end of the fast commissioning.
Values:
0:
No quick parameterization
1:
Quick parameterization after parameter reset
2:
Quick param. (only) for controller par. and reset for BICO par
3:
Completion of quick commissioning
Note:
When the calculations have been completed, p3900 and p0010 are automatically reset to a value of 0.
Description:
Exits the quick commissioning (p0010 = 1) with automatic calculation of all of the parameters that depend on the
entries made during the quick commissioning.
p3900 = 1 initially includes a parameter reset (factory setting, the same as p0970 = 1) for all parameters of the drive
object; however, without overwriting the entries made during the quick commissioning.
The interconnections of PROFIBUS PZD telegram selection (p0922) and the interconnections via p0700, p1000
and p1500 are re-established and all of the dependent motor, open-loop and control-loop control parameters are
calculated (corresponding to p0340 = 1).
p3900 = 2 includes the restoration of the interconnections of PROFIBUS PZD telegram selection (p0922) and the
interconnections via p0700, p1000 and p1500 and the calculations corresponding to p0340 = 1.
p3900 = 3 only includes the calculations associated with the motor, open-loop and closed-loop control parameters
corresponding to p0340 = 1.
Values:
0:
No quick parameterization
1:
Quick parameterization after parameter reset
2:
Quick parameterization (only) for BICO and motor parameters
3:
Quick parameterization for motor parameters (only)
Note:
When the calculations have been completed, p3900 and p0010 are automatically reset to a value of 0.
When calculating motor, open-loop and closed-loop control parameters (such as for p0340 = 1) parameters associ-
ated with a selected Siemens list motor are not overwritten.
Description:
Calibration factor for the DC link voltage measurement.
Caution:
Incorrect use of the calibration can have a negative impact on the closed-loop control. The parameter influences the
upper and lower voltage detection.
Note:
Parameter entries are directly saved in the DRIVE-CLiQ component involved. Only values from 100 ... 10000 are
accepted. All other entries are not saved and are therefore also not displayed.
The parameter only has an effect for chassis power units.
Calculation rule: p3902_new = p3902_old * r0026 / Vdc_measured value
p3900
Completion of quick commissioning / Compl quick_comm
SERVO, VECTOR
Can be changed:
C2(1)
Calculated:
-
Access level:
1
Data type:
Integer16
Dynamic index:
-
Func. diagram:
-
P-Group:
Displays, signals
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 3
0
p3902[0...n]
Power unit EEPROM Vdc calibration / PU EEPROM Vdc_cal
A_INF, B_INF,
SERVO, S_INF,
VECTOR
Can be changed:
C1, C2(1), T
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dynamic index:
PDS, p0120
Func. diagram:
-
P-Group:
-
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 4294967295
0
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...