![Siemens SINAMICS S Series Скачать руководство пользователя страница 1557](http://html.mh-extra.com/html/siemens/sinamics-s-series/sinamics-s-series_list-manual_12654271557.webp)
List of faults and alarms
Faults and Alarms
3-1557
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
A07504
Drive: Motor data set is not assigned to a drive data set
Drive object:
SERVO, TM41, VECTOR
Reaction:
NONE
Acknowledge:
NONE
Cause:
A motor data set is not assigned to a drive object.
All of the existing motor data sets in the drive data sets must be assigned using the MDS number (p0186[0...n]).
There must be at least as many drive data sets as motor data sets.
Alarm value (r2124, interpret decimal):
Number of the motor data set that has not been assigned.
Remedy:
In the drive data sets, assign the non-assigned motor data set using the MDS number (p0186[0...n]).
- check whether all of the motor data sets are assigned to drive data sets.
- if required, delete superfluous motor data sets.
- if required, set-up new drive data sets and assign to the corresponding motor data sets.
See also: p0186 (Motor Data Sets (MDS) number)
F07510
Drive: Identical encoder in the drive data set
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
More than one encoder with identical component number is assigned to a single drive data set. In one drive data set,
it is not permissible that identical encoders are operated together.
Fault value (r0949, interpret decimal):
1000 * first identical e 100 * second identical e drive data set.
Example:
Fault value = 1203 means:
In drive data set 3, the first (p0187[3]) and second encoder (p0188[3]) are identical.
Remedy:
Assign the drive data set to different encoders.
See also: p0141 (Encoder interface (Sensor Module) component number), p0187 (Encoder 1 encoder data set num-
ber), p0188 (Encoder 2 encoder data set number), p0189 (Encoder 3 encoder data set number)
F07511
Drive: Encoder used a multiple number of times
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
Each encoder may only be assigned to one drive and within a drive must - in each drive data set - either always be
encoder 1, always encoder 2 or always encoder 3. This unique assignment has been violated.
Fault value (r0949, interpret decimal):
The two parameters in coded form, that refer to the same component number.
First parameter:
Index: First and second decimal place (99 for EDS, not assigned DDS)
Parameter number: Third decimal place (1 for p0187, 2 for p0188, 3 for p0189, 4 for EDS not assigned DDS)
Drive number: Fourth and fifth decimal place
Second parameter:
Index: Sixth and seventh decimal place (99 for EDS, not assigned DDS)
Parameter number: Eighth decimal place (1 for p0187, 2 for p0188, 3 for p0189, 4 for EDS, not assigned DDS)
Drive number: Ninth and tenth decimal place
See also: p0141 (Encoder interface (Sensor Module) component number)
Remedy:
Correct the double use of a component number using the two parameters coded in the fault value.
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...