List of parameters
Parameters
1-419
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Dependency:
When the reference model is activate (p1400.3 = 1) and for an internal acceleration pre-control (p1400.2 = 0), the
acceleration pre-control is switched-out (disabled). The reference model (p1400.3 = 1) and external acceleration
pre-control (p1400.2 = 1) can be operated together.
Refer to: p0341, p0342
Note:
The parameter is set to 100% by the rotating measurement (refer to p1960).
The acceleration pre-control may not be used if the speed setpoint manifests significant ripple (e.g. analog setpoint)
and the rounding-off in the speed ramp-function generator is disabled.
We also recommend that the pre-control mode is not used if there is gearbox backlash.
Description:
Sets the signal source for scaling the moment of inertia.
Description:
Sets the signal source for scaling the motor weight.
Description:
Sets the load moment of inertia.
Note:
(p0341 * p0342) + p1498 influence the speed/torque pre-control in sensorless operation.
Description:
Sets the load mass.
Note:
(p0341 * p0342) + p1498 influence the velocity/force pre-control in sensorless operation.
p1497[0...n]
CI: Moment of inertia, scaling / M_mom inert scal
SERVO, VECTOR
(n/M)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / FloatingPoint32
Dynamic index:
CDS, p0170
Func. diagram:
5042, 5210,
6030, 6031
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
REL
Expert list:
1
Min Max
Factory
setting
- -
1
p1497[0...n]
CI: Motor weight scaling / Mot_weight scal
SERVO (Lin)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / FloatingPoint32
Dynamic index:
CDS, p0170
Func. diagram:
5042, 5210
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
REL
Expert list:
1
Min Max
Factory
setting
- -
1
p1498[0...n]
Load moment of inertia / Load mom of inert
SERVO
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
5042, 5210
P-Group:
Closed-loop control
Units group:
25_1
Unit selection:
p0100
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.00000 [kgm²]
100000.00000 [kgm²]
0.00000 [kgm²]
p1498[0...n]
Load mass / Load mass
SERVO (Lin)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
5042, 5210
P-Group:
Closed-loop control
Units group:
27_1
Unit selection:
p0100
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.00000 [kg]
10000.00000 [kg]
0.00000 [kg]
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...