List of parameters
Parameters
1-463
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Sets the denominator natural frequency for current setpoint filter 1 (PT2, general filter).
Dependency:
The current setpoint filters are parameterized with p1656 to p1676.
Description:
Sets the denominator damping for current setpoint filter 1.
Dependency:
The current setpoint filters are parameterized with p1656 to p1676.
Description:
Sets the numerator natural frequency for current setpoint filter 1 (general filter).
Dependency:
The current setpoint filters are parameterized with p1656 to p1676.
Description:
Sets the numerator damping for current setpoint filter 1.
Dependency:
The current setpoint filters are parameterized with p1656 to p1676.
Description:
Sets the current setpoint filter 2 as low pass (PT2) or as extended general 2nd-order filter.
Values:
1:
Low pass: PT2
2:
General 2nd-order filter
p1658[0...n]
Current setpoint filter 1 denominator natural frequency / I_set_filt 1 fn_n
SERVO, VECTOR
(n/M)
Can be changed:
U, T
Calculated:
CALC_MOD_CON
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
5710, 6710
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
REL
Expert list:
1
Min Max
Factory
setting
0.5 [Hz]
16000.0 [Hz]
1999.0 [Hz]
p1659[0...n]
Current setpoint filter 1 denominator damping / I_set_filt 1 D_n
SERVO, VECTOR
(n/M)
Can be changed:
U, T
Calculated:
CALC_MOD_CON
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
5710, 6710
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
REL
Expert list:
1
Min Max
Factory
setting
0.001 10.000
0.700
p1660[0...n]
Current setpoint filter 1 numerator natural frequency / I_set_filt 1 fn_z
SERVO, VECTOR
(n/M)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
5710, 6710
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
REL
Expert list:
1
Min Max
Factory
setting
0.5 [Hz]
16000.0 [Hz]
1999.0 [Hz]
p1661[0...n]
Current setpoint filter 1 numerator damping / I_set_filt 1 D_z
SERVO, VECTOR
(n/M)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
5710, 6710
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
REL
Expert list:
1
Min Max
Factory
setting
0.000 10.000
0.700
p1662[0...n]
Current setpoint filter 2 type / I_set_filt 2 Typ
SERVO, VECTOR
(n/M)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Integer16
Dynamic index:
DDS, p0180
Func. diagram:
5710, 6710
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
REL
Expert list:
1
Min Max
Factory
setting
1 2
1
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...