Faults and Alarms
List of faults and alarms
3-1570
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
A07597 (F)
Encoder 2: Reference function interrupted
Drive object:
SERVO, VECTOR
Reaction:
NONE
Acknowledge:
NONE
Cause:
An activated reference function (reference mark search or measuring probe evaluation) was interrupted.
- an encoder fault has occurred (Gn_ZSW.15 = 1).
- position actual value was set during an activated reference function.
- simultaneously activate reference mark search and measuring probe evaluation (BI: p2508 and BI: p2509 = 1 sig-
nal).
- activated reference function (reference mark search or measuring probe evaluation) was de-activated (BI: p2508
and BI: p2509 = 0 signal).
Remedy:
- check the causes and resolve.
- reset the control (BI: p2508 and BI: p2509 = 0 signal) and activate the requested function.
Reaction upon F:
OFF1 (OFF2, OFF3)
Acknowl. upon F:
IMMEDIATELY
A07598 (F)
Encoder 3: Reference function interrupted
Drive object:
SERVO, VECTOR
Reaction:
NONE
Acknowledge:
NONE
Cause:
An activated reference function (reference mark search or measuring probe evaluation) was interrupted.
- an encoder fault has occurred (Gn_ZSW.15 = 1).
- position actual value was set during an activated reference function.
- simultaneously activate reference mark search and measuring probe evaluation (BI: p2508 and BI: p2509 = 1 sig-
nal).
- activated reference function (reference mark search or measuring probe evaluation) was de-activated (BI: p2508
and BI: p2509 = 0 signal).
Remedy:
- check the causes and resolve.
- reset the control (BI: p2508 and BI: p2509 = 0 signal) and activate the requested function.
Reaction upon F:
OFF1 (OFF2, OFF3)
Acknowl. upon F:
IMMEDIATELY
F07800
Drive: No power unit present
Drive object:
A_INF, B_INF, SERVO, S_INF, VECTOR
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The power unit parameters cannot be read or no parameters are stored in the power unit.
Connection between the CU and the Motor Module was interrupted or is defective.
This fault also occurs if an incorrect topology was selected in the commissioning software and this parameterization
is then downloaded into the CU.
See also: r0200 (Power unit, actual code number)
Remedy:
- connect the data line to power unit and restart the Control Unit (POWER ON).
- check or replace the CU module.
- check the cable between the CU and Motor Module.
- after correcting the topology, the parameters must be again downloaded using the commissioning software.
F07801
Drive: Motor overcurrent
Drive object:
SERVO
Reaction:
OFF2 (NONE, OFF1, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
The permissible motor limit current was exceeded.
- effective current limit set too low.
- current controller not correctly set.
- motor was braked with an excessively high stall torque correction factor.
- V/f operation: Up ramp was set too short or the load is too high.
- V/f operation: Short-circuit in the motor cable or ground fault.
- V/f operation: Motor current does not match the current of Motor Module.
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...