List of parameters
Parameters
1-401
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
The following sources are available for the displayed setpoint:
- setpoint at the ramp-function generator input (r1119).
- speed setpoint 1 (p1155).
- speed setpoint 2 (p1160).
- speed setpoint for the speed pre-control (p1430).
- setpoint from DSC (for DSC active).
- setpoint via PC (for master control active, p3983).
Dependency:
Refer to: r1119, p1155, p1160, p1430
Description:
Displays the sum of all velocity setpoints that are present.
The following sources are available for the displayed setpoint:
- setpoint at the ramp-function generator input (r1119).
- velocity setpoint 1 (p1155).
- velocity setpoint 2 (p1160).
- velocity setpoint for the velocity pre-control (p1430).
- setpoint from DSC (for DSC active).
- setpoint via PC (for master control active, p3983).
Dependency:
Refer to: r1119, p1155, p1160, p1430
Description:
Displays the actual, smoothed actual speed for speed control.
Description:
Sets the smoothing time for the actual speed of the speed controller for sensorless closed-loop speed control.
Note:
The smoothing must be increased if there is gear backlash. For longer smoothing times, the integral time of the
speed controller must also be increased (e.g. using p0340 = 4).
r1444
Velocity controller, velocity setpoint, total / v_ctrl v_set stat
SERVO (Lin)
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
5030
P-Group:
Closed-loop control
Units group:
4_1
Unit selection:
p0505
Not for motor type:
REL
Expert list:
1
Min Max
Factory
setting
- [m/min]
- [m/min]
- [m/min]
r1445
CO: Actual speed, smoothed / n_ist smooth
VECTOR (n/M)
Can be changed:
-
Calculated:
-
Access level:
4
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
6040
P-Group:
Closed-loop control
Units group:
3_1
Unit selection:
p0505
Not for motor type:
REL
Expert list:
1
Min Max
Factory
setting
- [RPM]
- [RPM]
- [RPM]
p1452[0...n]
Speed controller speed actual value smoothing time (SLVC) / n_C n_act T_s SLVC
VECTOR (n/M)
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
6040
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
REL
Expert list:
1
Min Max
Factory
setting
0.00 [ms]
32000.00 [ms]
10.00 [ms]
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...