Description:
Sets the smoothing time constant of the accelerating force.
Note:
For servo drives, the parameter is only effective in sensorless operation.
Description:
Displays the accelerating torque to pre-control the speed controller for torque-speed pre-control (p1402.4 = 1 or in
sensorless operation).
Index:
[0] = Unsmoothed
[1] = Smoothed
Dependency:
Refer to: p0341, p0342, p1300, p1402, r1493, p1497, p1498
Description:
Displays the accelerating torque to pre-control the velocity controller for force- velocity pre-control (p1402.4 = 1 or in
sensorless operation).
Index:
[0] = Unsmoothed
[1] = Smoothed
Dependency:
Refer to: p0341, p0342, p1300, p1402, r1493, p1497, p1498
Description:
Displays the accelerating torque for pre-control of the speed controller.
Index:
[0] = Unsmoothed
[1] = Smoothed
Dependency:
Refer to: p0341, p0342, p1496
p1517[0...n]
Acceleration force smoothing time constant / F_accel T_smooth
SERVO (Lin)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
5042, 5210
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
REL
Expert list:
1
Min Max
Factory
setting
0.00 [ms]
100.00 [ms]
4.00 [ms]
r1518[0...1]
CO: Accelerating torque / M_accel
SERVO
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
5042, 5210
P-Group:
Closed-loop control
Units group:
7_1
Unit selection:
p0505
Not for motor type:
REL
Expert list:
1
Min Max
Factory
setting
- [Nm]
- [Nm]
- [Nm]
r1518[0...1]
CO: Accelerating force / F_accel
SERVO (Lin)
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
5042, 5210
P-Group:
Closed-loop control
Units group:
8_1
Unit selection:
p0505
Not for motor type:
REL
Expert list:
1
Min Max
Factory
setting
- [N]
- [N]
- [N]
r1518[0...1]
CO: Accelerating torque / M_accel
VECTOR (n/M)
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
6060
P-Group:
Closed-loop control
Units group:
7_1
Unit selection:
p0505
Not for motor type:
REL
Expert list:
1
Min Max
Factory
setting
- [Nm]
- [Nm]
- [Nm]
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...