Parameters
List of parameters
1-908
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Dependency:
Refer to: p0121, p0141, p0151, p7829
Note:
For p7828[0] = 399, the firmware for all of the existing components is downloaded.
The firmware download is started with p7829 = 1.
Description:
Activating the firmware download for the DRIVE-CLiQ components specified in p7828.
1: Activate download.
0: Download successfully completed.
1: Fault code
011: DRIVE-CLiQ component has detected a checksum error.
015: The selected DRIVE-CLiQ components did not accept the contents of the firmware file.
018: Firmware version is too old and is not accepted by the component.
019: Firmware version is not suitable for the hardware release of the component.
101: After several communication attempts, not response from the DRIVE-CLiQ component.
140: Firmware file for the DRIVE-CLiQ component not available on the CompactFlash card.
143: Component is not changed in the firmware download mode.
156: Component with the specified component number is not available.
Additional values:
Only for internal Siemens troubleshooting.
Dependency:
Refer to: p7828
Note:
p7829 is automatically set to 0 after the firmware has been successfully downloaded.
The new firmware only becomes active at the next system run-up.
Description:
Selects a telegram whose contents should be shown in p7831 ... p7836.
Values:
0:
Reserved
1:
First cyclic receive telegram sensor 1
2:
First cyclic receive telegram sensor 2
3:
First cyclic receive telegram sensor 3
Dependency:
Refer to: r7831, r7832, r7833, r7834, r7835, r7836
Description:
Displays the signals contained in the selected telegram (p7830).
p7829
Activate firmware download / FW download act
CU_CX32, CU_S
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Integer16
Dynamic index:
-
Func. diagram:
-
P-Group:
-
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 999
0
p7830
Diagnostics telegram selection / Diag telegram
SERVO, VECTOR
Can be changed:
T
Calculated:
-
Access level:
4
Data type:
Integer16
Dynamic index:
-
Func. diagram:
-
P-Group:
-
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 3
0
r7831[0...15]
Telegram diagnostics signals / Tel diag signals
SERVO, VECTOR
Can be changed:
-
Calculated:
-
Access level:
4
Data type:
Integer16
Dynamic index:
-
Func. diagram:
-
P-Group:
-
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 10789
-
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...