Faults and Alarms
List of faults and alarms
3-1504
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Remedy:
Use a SERVO / VECTOR drive object with the corresponding number.
Note:
The alarm is reset as follows:
- remove the cause of this alarm.
- restart the function generator.
A02008
Function generator: Drive specified a multiple number of times
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The drive object specified for connection is already specified.
Alarm value (r2124, interpret decimal):
Drive object number of the drive object that is specified a multiple number of times.
Remedy:
Specify a different drive object.
Note:
The alarm is reset as follows:
- remove the cause of this alarm.
- restart the function generator.
A02009
Function generator: Illegal mode
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The selected operating mode (p1300) of the drive object is not permissible when using the function generator.
Alarm value (r2124, interpret decimal):
Number of the drive object involved.
Remedy:
Change the operating mode for this drive object to p1300 = 20 (sensorless speed control) or p1300 = 21 (speed con-
trol with encoder).
Note:
The alarm is reset as follows:
- remove the cause of this alarm.
- restart the function generator.
A02010
Function generator: Speed setpoint from the drive is not zero
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The speed setpoint of a drive - selected to be connected to - is greater than the value for the standstill detection set
using p1226.
Alarm value (r2124, interpret decimal):
Number of the drive object involved.
Remedy:
For all of the drives specified for connection, set the speed setpoints to 0.
Note:
The alarm is reset as follows:
- remove the cause of this alarm.
- restart the function generator.
A02011
Function generator: The actual drive speed is not zero
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The speed actual value of a drive - selected to be connected to - is greater than the value for the standstill detection
set using p1226.
Alarm value (r2124, interpret decimal):
Number of the drive object involved.
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...