Parameters
List of parameters
1-584
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Sets the hysteresis speed (bandwidth) for the following signals:
"|n_act| < = speed threshold value 2" (BO: r2197.1)
"|n_act| > speed threshold value 2" (BO: r2197.2)
Dependency:
Refer to: p2155, r2197
Description:
Sets the hysteresis velocity (bandwidth) for the following signals:
"|n_act| < = speed threshold value 2" (BO: r2197.1)
"|n_act| > speed threshold value 2" (BO: r2197.2)
Dependency:
Refer to: p2155, r2197
Description:
Sets the speed threshold value for the signal "f or n comparison value reached or exceeded" (BO: r2199.1).
Dependency:
Refer to: p2142, r2199
Description:
Sets the velocity threshold value for the signal "f or n comparison value reached or exceeded" (BO: r2199.1).
Dependency:
Refer to: p2142, r2199
p2140[0...n]
Hysteresis speed 2 / n_hysteresis 2
SERVO, VECTOR
Can be changed:
U, T
Calculated:
CALC_MOD_LIM_REF
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
8010
P-Group:
Messages
Units group:
3_1
Unit selection:
p0505
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.00 [RPM]
300.00 [RPM]
90.00 [RPM]
p2140[0...n]
Hysteresis velocity 2 / v_hysteresis 2
SERVO (Lin)
Can be changed:
U, T
Calculated:
CALC_MOD_LIM_REF
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
8010
P-Group:
Messages
Units group:
4_1
Unit selection:
p0505
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.00 [m/min]
10.00 [m/min]
0.90 [m/min]
p2141[0...n]
Speed threshold 1 / n_thresh val 1
SERVO, VECTOR
Can be changed:
U, T
Calculated:
CALC_MOD_LIM_REF
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
8010
P-Group:
Messages
Units group:
3_1
Unit selection:
p0505
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.00 [RPM]
210000.00 [RPM]
5.00 [RPM]
p2141[0...n]
Velocity threshold value 1 / v_thresh val 1
SERVO (Lin)
Can be changed:
U, T
Calculated:
CALC_MOD_LIM_REF
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
8010
P-Group:
Messages
Units group:
4_1
Unit selection:
p0505
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.00 [m/min]
1000.00 [m/min]
0.05 [m/min]
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...