Parameters
List of parameters
1-416
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Sets the source for droop feedback.
Values:
0:
Droop feedback not connected
1:
Droop from torque setpoint
2:
Droop from speed controller output
3:
Droop from integral output, speed controller
Dependency:
Refer to: p1489, r1490, p1492
Description:
Sets the scaling for the droop feedback
Dependency:
Refer to: p1488, r1490, p1492
Note:
Example:
A value of 0.05 means that for a torque equal to the rated motor torque, the rated motor speed is reduced by 5 %.
Description:
Displays the output signal of the droop calculation. The droop feedback result is subtracted from the speed setpoint
when activated (p1492).
Dependency:
Refer to: p1488, p1489, p1492
Description:
Enables the droop to be applied to the speed/velocity setpoint.
Dependency:
Refer to: p1488, p1489, r1490
Note:
Even when not enabled, the droop speed is calculated but not subtracted from the setpoint speed. This makes it
possible to subtract the result of this calculation from the speed of another drive.
p1488[0...n]
Droop input source / Droop input,source
VECTOR (n/M)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Integer16
Dynamic index:
DDS, p0180
Func. diagram:
6030
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
REL
Expert list:
1
Min Max
Factory
setting
0 3
0
p1489[0...n]
Droop feedback scaling / Droop scaling
VECTOR (n/M)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
6030
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
REL
Expert list:
1
Min Max
Factory
setting
0.000 0.500
0.050
r1490
CO: Droop feedback speed reduction / Droop n_reduction
VECTOR (n/M)
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
6030
P-Group:
Closed-loop control
Units group:
3_1
Unit selection:
p0505
Not for motor type:
REL
Expert list:
1
Min Max
Factory
setting
- [RPM]
- [RPM]
- [RPM]
p1492[0...n]
BI: Droop feedback enable / Enables droop
VECTOR (n/M)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dynamic index:
CDS, p0170
Func. diagram:
-
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
REL
Expert list:
1
Min Max
Factory
setting
- -
0
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...