Faults and Alarms
List of faults and alarms
3-1486
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Remedy:
Either de-select the function "actual value synchronization" or the monitoring functions with absolute reference
(SCA/SLP) and carry out a POWER ON.
Note:
SCA: Safe Cam / SN: Safe software cam
SI: Safety Integrated
SLP: Safely-Limited Position / SE: Safe software limit switches
See also: p9501 (SI motion enable safety functions (Control Unit))
C01689
SI Motion: Axis re-configured
Drive object:
SERVO, VECTOR
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
The axis configuration was changed (e.g. changeover between linear axis and rotary axis).
Parameter p0108.13 is internally set to the correct value.
Fault value (r0949, interpret decimal):
Parameter number that initiated the change.
See also: p9502 (SI motion axis type (Control Unit))
Remedy:
The following should be carried out after the changeover:
- exit the safety commissioning mode (p0010).
- save the parameters.
- carry out a POWER ON.
Note:
For the commissioning software, the units are only consistently displayed after a project upload.
F01690
SI Motion: Data save problem for the NVRAM
Drive object:
All objects
Reaction:
A_INFEED: NONE (OFF1, OFF2)
SERVO: NONE (OFF1, OFF2, OFF3)
VECTOR: NONE (OFF1, OFF2, OFF3)
Acknowledge:
POWER ON
Cause:
For the safety functionality logbook when saving parameters p9781 and p9782, there was not enough
NVRAM available in the drive:
0: There is no physical NVRAM available in the drive.
1: There is no NVRAM free.
Remedy:
0: Use a drive with NVRAM or add NVRAM.
1: By de-selecting functions that are not required, create sufficient space in the drive NVRAM.
A01696 (F)
SI Motion: Testing of the motion monitoring functions selected when booting
Drive object:
SERVO, VECTOR
Reaction:
NONE
Acknowledge:
NONE
Cause:
The test of the motion monitoring functions was already illegally active when booting.
In order to avoid an incorrect alarm, the test is only carried out after again selecting the forced checking procedure
parameterized in p9705.
Note:
This message does not result in a safety stop response.
See also: p9705 (SI Motion: Test stop signal source)
Remedy:
De-select the forced checking procedure of the safety motion monitoring functions and then select again.
The signal source for initiation is parameterized in BI: p9705.
Note:
SI: Safety Integrated
See also: p9705 (SI Motion: Test stop signal source)
Reaction upon F:
NONE (OFF1, OFF2, OFF3)
Acknowl. upon F:
IMMEDIATELY (POWER ON)
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...