List of parameters
Parameters
1-243
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Sets the signal source to select the Drive Data Set, bit 4 (DDS, bit 4).
Dependency:
Refer to: r0051, r0837
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description:
Sets the freely-assignable motor number for the motor changeover.
Dependency:
Refer to: p0827
Caution:
When changing over motor data sets with the same motor number (e.g. star/delta changeover) and for a motor with
brake, the motor brake remains open during the changeover.
Note:
When the motor data sets are changed-over, the following applies:
The same motor number signifies the same thermal model.
Description:
Sets the bit number for every motor data set.
Example:
p0827[0] = 0: For MDS0, r0830.0 is switched.
p0827[1] = 5: For MDS1, r0830.5 is switched.
Dependency:
Refer to: p0826, r0830
Note:
A motor is only changed over (a new motor selected) after the pulses have been canceled.
When the motor data sets are changed-over, the following applies:
Bit numbers that are not identical, signify that the motor must be changed over.
Description:
Sets the signal source for the feedback signal when changing over the motor.
For p0833.0 = 1 the following applies:
p0824[0...n]
BI: Drive data set selection DDS bit 4 / DDS select., bit 4
SERVO, TM41, VEC-
TOR
Can be changed:
C2(15), T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dynamic index:
CDS, p0170
Func. diagram:
8565
P-Group:
Data sets
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
0
p0826[0...n]
Motor changeover, motor number / Mot_chng mot No.
SERVO, VECTOR
Can be changed:
C2(3), U
Calculated:
-
Access level:
2
Data type:
Unsigned16
Dynamic index:
MDS, p0130
Func. diagram:
8575
P-Group:
Motor
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 15
0
p0827[0...n]
Motor changeover status word bit number / Mot_chg ZSW bitNo.
SERVO, VECTOR
Can be changed:
C2(3), U
Calculated:
-
Access level:
2
Data type:
Unsigned16
Dynamic index:
MDS, p0130
Func. diagram:
8575
P-Group:
Motor
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 15
0
p0828[0...n]
BI: Motor changeover, feedback signal / Mot_chng fdbk sig
SERVO, VECTOR
Can be changed:
C2(3), T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dynamic index:
CDS, p0170
Func. diagram:
8575
P-Group:
Motor
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
0
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...