List of parameters
Parameters
1-491
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Dependency:
Refer to: p1802
Note:
During operation (the pulses enabled) the configuration cannot be changed by changing-over drive data sets.
Description:
Status of the actual value correction
Description:
Sets the weighting factor for the leakage inductance of the L-R element of the actual value correction.
Description:
Sets the damping factor for the actual value correction.
The factor multiplies the T0/Tsig ratio in the feedback branch of the LR element
Description:
Displays phase correction currents as well as the drive converter phase currents
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Actual value correction de-activated
Yes
No
-
01
Compares the integrals from modulator and
setpoint
Yes
No
-
r1841
Actual value correction status word / AVC status
VECTOR
Can be changed:
-
Calculated:
-
Access level:
4
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
-
P-Group:
Modulation
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Hardware for the actual value correction
detected
Yes
No
-
01
Automatic shutdown (too many switching
instants)
Yes
No
-
02
Integral normalized to half the gating unit
clock cycle freq.
Yes
No
-
03
Actual value correction temporarily sup-
pressed
Yes
No
-
15
Actual value correction active
Yes
No
-
p1845[0...n]
Actual value correction evaluation factor Lsig / ActV_corr FactLsig
VECTOR
Can be changed:
U, T
Calculated:
-
Access level:
4
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
-
P-Group:
Modulation
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.00 10.00
1.00
p1846[0...n]
Actual value correction damping factor / ActV_corr D_factor
VECTOR
Can be changed:
U, T
Calculated:
-
Access level:
4
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
-
P-Group:
Modulation
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.00 10.00
1.00
r1848[0...5]
Actual value correction phase currents / ActVal_corr I_corr
VECTOR
Can be changed:
-
Calculated:
-
Access level:
4
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Modulation
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...