![Siemens SINAMICS S Series Скачать руководство пользователя страница 1729](http://html.mh-extra.com/html/siemens/sinamics-s-series/sinamics-s-series_list-manual_12654271729.webp)
List of faults and alarms
Faults and Alarms
3-1729
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
F35228
TM: Sampling time p4099[3] invalid
Drive object:
TM41
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The value of the cycle time for the incremental encoder emulation, specified in p4099[3] does not correspond to a
valid value.
The system already changed the p4099[3] to a valid value.
The parameters of the TM41 involved must be saved on the CompactFlash card and a POWER ON carried out.
Remedy:
F35229
TM time slice de-activated
Drive object:
TM41
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The required value of a cycle time in P4099 () is invalid.
The corresponding time slice was not activated.
Alarm value:
0 Digital input/outputs ( P4099(0) )
1 Analog input ( P4099 (1) )
3 Encoder emulation position setpoint ( P4099 (3) )
4 Encoder emulation speed setpoint ( P4099 (3) )
5 Encoder emulation speed setpoint ( P4099 (3) )
6 Internal sequencer of the TM41 (internal error)
Remedy:
The sampling time P4099 (0) may not be zero. Change the sampling time corresponding to the error code.
F35230
HW problem with the TM module
Drive object:
A_INF, B_INF, CU_LINK, DMC20, SERVO, S_INF, TB30, TM15, TM15DI_DO, TM17, TM31, TM41, TM54F_MA,
TM54F_SL, VECTOR
Reaction:
A_INFEED: OFF1 (NONE, OFF2)
SERVO: NONE
VECTOR: NONE
Acknowledge:
POWER ON
Cause:
The terminal module used has signaled an internal error. Signals of this module may not be evaluated and are poten-
tially incorrect.
Remedy:
The module must be replaced if no other alarms that refer to a communications error are present in the system.
N35800 (F)
TM: Group signal
Drive object:
All objects
Reaction:
A_INFEED: OFF2 (NONE, OFF1)
SERVO: OFF2 (IASC / DCBRAKE, NONE, OFF1, OFF3, STOP1, STOP2)
VECTOR: OFF2 (IASC / DCBRAKE, NONE, OFF1, OFF3, STOP1, STOP2)
Acknowledge:
NONE
Cause:
The Terminal Module has detected at least one fault.
Remedy:
Evaluates other actual messages.
Reaction upon F:
A_INFEED: OFF2 (NONE, OFF1)
SERVO: OFF2 (IASC / DCBRAKE, NONE, OFF1, OFF3, STOP1, STOP2)
VECTOR: OFF2 (IASC / DCBRAKE, NONE, OFF1, OFF3, STOP1, STOP2)
Acknowl. upon F:
IMMEDIATELY
A35801 (F, N)
TM DRIVE-CLiQ: Sign-of-life missing
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
A DRIVE-CLiQ communications error has occurred between the Control Unit and the Terminal Module involved.
Alarm value (r2124, interpret hexadecimal):
0A: The sign-of-life bit in the receive telegram is not set.
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...