![Siemens SINAMICS S Series Скачать руководство пользователя страница 240](http://html.mh-extra.com/html/siemens/sinamics-s-series/sinamics-s-series_list-manual_1265427240.webp)
Parameters
List of parameters
1-240
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Sets the signal source to block the master control.
Dependency:
Refer to: r0807
Note:
The master control is used from the commissioning software (drive control panel) and from the Advanced Operator
Panel (AOP, LOCAL mode).
Description:
Displays what has the master control.
The drive can be controlled via the BICO interconnection or from external (e.g. the commissioning software).
Dependency:
Refer to: p0806
Notice:
The master control only influences control word 1 and speed setpoint 1. Other control words/setpoints can be trans-
ferred from another automation device.
Note:
Bit 0 = 0: BICO interconnection active
Bit 0 = 1: Master control for PC/AOP
The master control is used from the commissioning software (drive control panel) and from the Advanced Operator
Panel (AOP, LOCAL mode).
Description:
Copies one Command Data Set (CDS) into another.
Index:
[0] = Source Command Data Set
[1] = Target command data set
[2] = Start copying
Note:
Procedure:
1. In Index 0, enter which command data set should be copied.
2. In Index 1, enter the command data set that is to be copied into.
3. Start copying: Set index 2 from 0 to 1.
p0809[2] is automatically set to 0 when copying is completed.
p0806
BI: Inhibit master control / PcCtrl inhibit
A_INF, B_INF,
SERVO, S_INF,
VECTOR
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dynamic index:
-
Func. diagram:
-
P-Group:
Commands
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
0
r0807.0
BO: Master control active / PcCtrl active
A_INF, B_INF,
SERVO, S_INF,
VECTOR
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
Unsigned8
Dynamic index:
-
Func. diagram:
-
P-Group:
Displays, signals
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Master control active
Yes
No
5030
p0809[0...2]
Copy Command Data Set CDS / Copy CDS
SERVO, VECTOR
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Unsigned8
Dynamic index:
-
Func. diagram:
8560
P-Group:
Commands
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 15
0
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...