Description:
Sets the signal source to select the required input value for the multiplexer.
CI: p3572 = 0, 1, 2, 3 --> valid values
Fault F06320 is output for other values.
Dependency:
Refer to: p3571, r3573
Refer to: F06320
Note:
For a master infeed and a slave infeed, the active current setpoint can be entered without using a multiplexer. If the
multiplexer for the master/slave is not required, then it can also be used for another function.
Description:
Displays (connector output) the output for the multiplexer.
The signal value is used as standard for the active current setpoint for the slave infeed.
Dependency:
Refer to: p3570, p3571, p3572
Note:
For a master infeed and a slave infeed, the active current setpoint can be entered without using a multiplexer. If the
multiplexer for the master/slave is not required, then it can also be used for another function.
Description:
Sets the upper and lower limit values and hysteresis values for the DC link voltage monitoring.
The values are entered as absolute values and refer to the DC link voltage setpoint (p3510).
For a slave infeed, if the limits are violated, then the closed-loop voltage control is automatically switched-in.
Index:
[0] = Vdc upper limit value
[1] = Vdc lower limit value
[2] = Vdc upper hysteresis value
[3] = Vdc lower hysteresis value
Dependency:
Refer to: p0210
p3572
CI: Master/slave active current setpoint, multiplexer selection / I_act multi sel
A_INF (Mas-
ter/Slave)
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Integer16
Dynamic index:
-
Func. diagram:
8948
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
0
r3573
CO: Master/slave active current setpoint, multiplexer output / I_act multi outp
A_INF (Mas-
ter/Slave)
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
8948
P-Group:
Closed-loop control
Units group:
6_2
Unit selection:
p0505
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- [Arms]
- [Arms]
- [Arms]
p3574[0...3]
Master/slave DC link voltage monitoring / Vdc monitoring
A_INF (Mas-
ter/Slave)
Can be changed:
C2(1), T
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
8948
P-Group:
Converter
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
-60 [V]
60 [V]
[0] 20 [V]
[1] -20 [V]
[2] 5 [V]
[3] -5 [V]
Содержание SINAMICS S Series
Страница 1: ...sinamics s SINAMICS S List Manual 07 2007 ...
Страница 2: ......
Страница 1422: ...Function Diagrams Braking Module external 2 1422 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1750: ...Faults and Alarms List of faults and alarms 3 1750 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1778: ...Appendix List for motor code encoder code A 1778 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...
Страница 1812: ...Index D 1812 Siemens AG 2007 All Rights Reserved SINAMICS S List Manual LH1 07 2007 ...